036-21035-002-D-0602 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D1HG/D1HE 180 & 240 15 & 20 NOMINAL TONS 10.00 EER (15 TONS), 9.7 EER (20 TONS) TECHNICAL GUIDE TECHNICAL GUIDE ® DESCRIPTION YORK Sunline PLUS II units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. All units include: Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards Two-stage cooling provided by dual independent refrig- eration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freez- estats Hermetically sealed compressors with crankcase heat- ers Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic Permanently lubricated motors Bottom or side air discharge configuration capability (field convertible) Belt Drive Blower Motor Manufactured under the quality standards of ISO9001 Twenty-four volt control circuit with compressor lock-out Zero-25% fixed air damper with hood Copper tube/aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Single point power connection Complete factory package - tested, charged and wired ETL & CGA agency approvals on all units Factory Limited Parts Warranty One-year parts warranty A Five-years part warranty on the compressor and elec- tric heat elements. Ten-year Part Warranty on the gas-fired heat exchang- ers.

Upload: holly-keptitreal

Post on 07-Mar-2015

235 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE AIR

CONDITIONERS

D1HG/D1HE 180 & 240

15 & 20 NOMINAL TONS

10.00 EER (15 TONS), 9.7 EER (20 TONS)

TECHNICALGUIDETECHNICALGUIDE

� �

DESCRIPTIONYORK Sunline PLUS II units are convertible single packagehigh efficiency rooftops. All models have independent dualrefrigerant circuits for efficient part load operation. Althoughthe units are primarily designed for curb mounting on a roof,they can also be slab-mounted at ground level or set on steelbeams above a finished roof.

All units include:

• Powder Paint finish that meets ASTM-B-117 750 hoursalt spray standards

• Two-stage cooling provided by dual independent refrig-eration circuits with expansion valves, filter-driers, highand low pressure/loss of charge switches and freez-estats

• Hermetically sealed compressors with crankcase heat-ers

• Two-stage heating provided by dual independent heatexchangers with aluminized steel tubes, redundant gasvalves, spark ignition with induced draft logic

• Permanently lubricated motors

• Bottom or side air discharge configuration capability(field convertible)

• Belt Drive Blower Motor

• Manufactured under the quality standards of ISO9001

• Twenty-four volt control circuit with compressor lock-out

• Zero-25% fixed air damper with hood

• Copper tube/aluminum fin coils

• Easy access to all components

• Rigging holes in base rails for lifting

• Single point power connection

• Complete factory package - tested, charged and wired

• ETL & CGA agency approvals on all units

• Factory Limited Parts Warranty

• One-year parts warranty

• A Five-years part warranty on the compressor and elec-tric heat elements.

• Ten-year Part Warranty on the gas-fired heat exchang-ers.

Page 2: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

2 Unitary Products Group

TABLE OF CONTENTS

pg.

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5

FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . 6

LIST OF FIGURES

# pg.

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 DHG/DHE FIELD WIRING DIAGRAM . . . . . . . . 23

3 UNIT DIMENSIONS FRONT VIEW . . . . . . . . . . 24

4 UNIT DIMENSIONS REAR VIEW . . . . . . . . . . . 25

5 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . 25

6 UNIT DIMENSIONS RAINHOOD . . . . . . . . . . . . 26

7 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . 26

8 UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . 27

9 UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . 27

10 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . 28

11 ROOF CURB DUCT OPENINGS DIMENSION . 28

12 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . 28

13 TYPICAL ROOFTOP INSTALLATION . . . . . . . . 29

LIST OF TABLES

1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . 4

2 SOUND POWER RATING . . . . . . . . . . . . . . . . . . 7

3 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . 7

4 GAS HEAT RATIINGS . . . . . . . . . . . . . . . . . . . . . 7

5 COOLING CAP FOR DHE/DHG 180 AT 85°F . . . 8

6 COOLING CAP FOR DHE/DHG 180 AT 95°F . . . 9

7 COOLING CAP FOR DHE/DHG 180 AT 105°F . 10

# pg.

8 COOLING CAP FOR DHE/DHG 180 AT 115°F . 11

9 COOLING CAP FOR DHE/DHG 240 AT 85°F . . 12

10 COOLING CAP FOR DHE/DHG 240 AT 95°F . . 13

11 COOLING CAP FOR DHE/DHG 240 AT 105°F . 14

12 COOLING CAP FOR DHE/DHG 240 AT 115°F . 15

13 DHG 15 TON SUPPLY AIR BLOWER PERF . . 16

14 DHG 20 TON SUPPLY AIR BLOWER PERF . . 17

15 DHE 15 TON SUPPLY AIR BLOWER PERF . . 18

16 DHE 20 TON SUPPLY AIR BLOWER PERF . . 19

17 BLOWER MOTOR AND DRIVE DATA . . . . . . . 20

18 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . 20

19 POWER EXHAUST PERFORMANCE . . . . . . . . 20

20 DHG ELECTRICAL DATA . . . . . . . . . . . . . . . . . 21

21 DHG VOLTAGE LIMITATIONS . . . . . . . . . . . . . 21

22 DHE VOLTAGE LIMITATIONS . . . . . . . . . . . . . 21

23 DHE ELECTRICAL DATA . . . . . . . . . . . . . . . . . 21

24 ELEC DATA UNITS WITH SUPPL ELEC HEAT 22

25 ELECTRIC HEAT CORRECTION FACTORS . . 22

26 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 23

27 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 23

28 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 24

29 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 24

30 4 POINT LOADS WEIGHT DISTRIBUTION . . . 27

31 6 POINT LOADS WEIGHT DISTRIBUTION . . . 27

Page 3: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 3

D 1 HG 180 N 240 25 EC

All models are available with a wide variety of factory-mounted options and field-installed accessories to makethem suitable for almost every application.

All units are self-contained and assembled on full perimeterbase rails with holes in the four corners for overhead rigging.Every unit is completely piped, wired, charged and tested atthe factory to simplify the field installation and to provideyears of dependable operation.

All models (including those with an economizer) are suitablefor either bottom or horizontal duct connections. Models withpower exhaust are suitable for bottom duct connections only.For bottom duct, you remove the sheet metal panels from thesupply and return air openings through the base of the unit.For horizontal duct, you replace the supply and return airpanels on the rear of the unit with a side duct flange acces-sory.

All models are available with seven different outdoor airdamper options:

• Single enthalpy economizer

• Differential (dual) enthalpy economizer

• Single enthalpy economizer with power exhaust

• Differential (dual) enthalpy economizer with powerexhaust

• Single Dry Bulb Economizer

• Single Dry Bulb Economizer with power exhaust

• Motorized outdoor air damper

A fixed outdoor air intake assembly will be shipped in thereturn air compartment of all units ordered without an econo-mizer or motorized outdoor air damper option. The assemblyincludes a rain hood with a damper that can be set for 10, 15or 25% outdoor air. With bottom duct connections, the intake

damper assembly should be mounted over the opening in thereturn air panel. With horizontal ductwork, it should bemounted on the return air duct.

All supply air blowers are equipped with a belt drive that canbe adjusted to meet the exact requirements of the job. A highspeed drive accessory is available for applications with ahigher CFM and/or static pressure requirement.

All compressors include crankcase heat and internal pres-sure relief. Every refrigerant circuit includes an expansionvalve, a liquid line filter-drier, a discharge line high pressureswitch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components. Theunit control circuit includes a 75 VA transformer, a 24-volt cir-cuit breaker and a relay board with two compressor lockoutcircuits, a terminal strip for thermostat wiring, plus an addi-tional set of pin connectors to simplify the interface of addi-tional field controls.

All units have long lasting powder paint cabinets with 750hour salt spray test approval under ASTM-B117 procedures.

All 208/230 and 460-volt models are ETL approved. All 208/230 and 575-volt models are CGA approved.

All models include a one-year limited parts warranty on thecomplete unit. Compressors and electric heater elementscarry a five-year warranty. Aluminized steel tubular heatexchangers carry a 10-year parts warranty.

All gas heat units are built with two heating sections for twoequal stages of capacity control. Each section includes adurable heat exchanger with aluminized steel tubes, a redun-dant gas valve, spark ignition, power venting, an ignitionmodule for 100% shut-off and all of the safety controlsrequired to meet the latest ANSI standards.

TABLE 1: PRODUCT NOMENCLATURE

Model #Model Number

DescriptionOptions

D Product Category D = Air Cond., Single Package

1 Product Generation 1 = 1st Generation

HG Product Identifier HG = Gas/Electric HE = Electric/Electric

180 Nominal Cooling Capacity 180 = 15 Tons 240 = 20 Tons

N Factory Installed HeatA = No Heat InstalledE = Electric Heat

N = Natural Gas

240 Nominal Heating OutputCapacity

GAS240 = 240 MBH

320 = 320 MBH

25 Voltage Code 25 = 208/230-3-60 46 = 460-3-60

EC Factory InstalledOption Code

BG = Motorized Outdoor Air DamperFD = Sing. Input Econo.er w/ Pwr ExhaustEC = Single Input Economizer

CF = Dual Input Econo. w/ Pwr Exhaust

DK = Diff. Input Economizer

Page 4: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

4 Unitary Products Group

The gas supply piping can be routed into the heating com-partment through a hole in the base pan of the unit or througha knockout in the piping panel on the front of the unit.

All electric heat models are wired for a single power sourceand include a bank of nickel chromium elements mounted atthe discharge of the supply air blower to provide a high veloc-ity and uniform distribution of air across the heating elements.

Every element is fully protected against excessive currentand temperature by fuses and two thermal limit switches.

The power supply wiring can be routed into the control boxthrough a threaded pipe connection in the base pan of theunit or through a knockout in the wiring panel on the front ofthe unit.

FACTORY-INSTALLED OPTIONS• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assemblywith fully modulating spring-return monitor actuatorcapable of introducing up to 100% outdoor air with nomi-nal 1% leakage type dampers.

The enthalpy system contains one sensor that monitorsthe outdoor air and determines when the air is coolenough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and mustbe field-assembled before installing.

Power exhaust is not available as a field installed option.

• DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZ-ERS - Includes a slide-in / plug-in damper assembly withfully modulating spring-return monitor actuator capableof introducing up to 100% outdoor air with nominal 1%leakage type dampers.

This enthalpy system contain one sensor that monitorsthe outdoor air and one sensor that monitors the returnair. The logic module compares these two values andmodulates the dampers providing the maximum effi-ciency of economizer system.

The rainhood is painted to match the basic unit and mustbe field-assembled before installing.

• POWER EXHAUST - Both the single and differentialeconomizer options are available with power exhaust.Whenever the outdoor air intake dampers are opened forfree cooling, the exhaust fan will be energized to preventthe conditioned space from being over-pressurized dur-ing economizer operation.

The exhaust fan, motor and controls are installed andwired at the factory. The rain hood and the back-draftdamper need to be assembled and installed in the field.

FIGURE 1 : UNIT CUTAWAY

ELECTRICAL DISCONNECTMOUNTING LOCATION(Field installed)

KNOCKOUT FORSIDE CONTROL WIRING ENTRY

KNOCKOUT FORSIDE POWER WIRING ENTRY SIDE

TERMINAL BLOCK(For Single Point Power Supplywith Electric Heat)ELECTRIC\ELECTRIC UNITS

BOTTOM POWER & CONTROLWIRING ENTRY

KNOCKOUTS FOR SIDEGAS SUPPLY ENTRY

HOLE FOR BOTTOMGAS SUPPLY ENTRY

POWER VENTOR MOTORWITH POST PURGE CYCLEBELT-DRIVE

BLOWER MOTOR

FULL PERIMETER 14 GUAGE BASERAILS WITH LIFTING HOLES

1" NPTICONDENSATE DRAIN

SIDE AND BOTTOMSUPPLY & RETURN AIRDUCT OPENINGS(SIDE X SIDE)

OUTDOOR AIR OPENINGFOR SLIDE-IN/PLUG-ININTERNAL ECONOMIZER(OPTION)

2" DISPOSABLEFILTERS

ECONOMIZER HOOD

LONG LASTINGPOWDER PAINT FINISH

20 GAUGE ALUMINIZED STEELTUBULAR HEAT EXCHANGERS COPPER TUBE/ALUMINUM FIN

CONDENSER COILS

LOW VOLTAGE RELAY BOARDAND TERMINAL STRIP

GAS/ELECTRICUNIT SHOWN

ELECTRIC HEATER LOCATION(OPTIONAL ELECTRIC/ELECTRIC UNITS)

HIGH EFFICIENCY COMPRESSORSWITH CRANKCASE HEATERS

Page 5: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 5

The power exhaust option can only be used on bottomduct configurations.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER -Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to apre-set position whenever the supply air blower is oper-ating and will drive fully closed when the blower unitshuts down.

The rain hood is painted to match the basic unit andmust be field assembled before installing.

Power exhaust is not available as a field installed option.

• PHENOLIC COATED CONDENSER COIL - Specialcoating process that utilizes Technicoat 10-1" processes.Coating is applied by total immersion of the complete coilfor maximum protection.

• ELECTRIC HEATERS (DHE UNITS ONLY) wired forsingle point power supply. These nickel chromium heaterelements are provided with limit and automatic resetcapability to prevent operation at excessive tempera-tures.

FIELD-INSTALLED ACCESSORIES• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assemblywith fully modulating spring-return monitor actuatorcapable of introducing up to 100% outdoor air with nomi-nal 1% leakage type dampers.

The enthalpy system contains one sensor that monitorsthe outdoor air and determines when the air is coolenough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and mustbe field-assembled before installing.

Power exhaust is not available as a field installed option.

• DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZ-ERS - Includes a slide-in / plug-in damper assembly withfully modulating spring-return monitor actuator capableof introducing up to 100% outdoor air with nominal 1%leakage type dampers.

This enthalpy system contain one sensor that monitorsthe outdoor air and one sensor that monitors the returnair. The logic module compares these two values andmodulates the dampers providing the maximum effi-ciency of economizer system.

The rainhood is painted to match the basic unit and mustbe field-assembled before installing.

Power exhaust is not available as a field installed option.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER -Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens tosome pre-set position whenever the supply air blower is

operating and will drive fully closed when the blower unitshuts down.

The rain hood is painted to match the basic unit andmust be field assembled before installing.

Power exhaust is not available as a field installed option.

• ROOF CURBS - Fourteen-inch high roof curbs provide awater-tight seal between the unit and the finished roof.These full perimeter curbs meet the requirements of theNational Roofing Contractors Association (NRCA) andare shipped knocked-down for field assembly. They'redesigned to fit inside the base rails of the unit andinclude both a wood nailing strip and duct hanger sup-ports.

• ANTI-RECYCLE TIMERS - Two solid state timers pre-vent the compressors from short-cycling. Once a com-pressor is de-energized, it will remain de-energized forapproximately five minutes.

• HIGH ALTITUDE NATURAL GAS - Burner orifices andpilot orifices are provided for proper furnace operation ataltitudes up to 6,000 feet.

• PROPANE - Burner orifices, pilot orifices and gas valveparts are provided to convert a natural gas furnace topropane.

• HIGH ALTITUDE PROPANE - Burner orifices and pilotorifices are provided for proper furnace operation at alti-tudes up to 6,000 feet. This accessory supplements thebasic propane conversion kit.

• SIDE DUCT FLANGES - One-inch flanges replace thesupply and return air panels on the rear of the unit toaccommodate horizontal duct connections. Theseflanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return. Theycannot be used on units with power exhaust.

• BAROMETRIC RELIEF DAMPER - This damper acces-sory can be used to relieve internal building air pressureon units with an economizer without power exhaust. Thisaccessory includes a rain hood, a bird screen and a fullyassembled damper. With bottom duct connections, thedamper should be mounted over the opening in thereturn air panel. With horizontal ductwork, the accessoryshould be mounted on the return air duct.

• HIGH SPEED DRIVE - A smaller blower pulley and ashorter belt increase the speed of the supply air blowerfor applications with a higher CFM and/or static pressurerequirements.

• LOW AMBIENT CONTROLS TO 0°F (15 Tons) - Anautotransformer and a thermostat maintain stable sys-tem operation by reducing the speed of the #1 con-denser fan motor at low outdoor temperatures. The kitalso includes a 1-phase motor to replace the unit's stan-dard 3-phase condenser fan motor. Standard units canoperate down to 25°F.

Page 6: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

6 Unitary Products Group

• LOW AMBIENT CONTROLS TO 0°F (20 TON) - Anelectronic head pressure control is added to each refrig-eration system to maintain stable system operation atlow outside temperatures. The kit also includes a singlephase motor to replace the units 3-phase condenser fanmotor. One kit is needed for each refrigerant systemstandard unit can operate down to 45°F.

TABLE 2: SOUND POWER RATING1

UNITSIZE

CFMESP BLOWER

SOUND POWER (db 10-12 Watts)

Octave Band Centerline Frequency (Hz)SWLdB(A)

dB(A)@

10Ft.2IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000

180 8,000 1.00 1,080 4.60 99 99 89 82 84 77 72 67 89 56

240 8,000 1.00 1,120 6.65 102 102 92 85 87 80 75 70 92 59

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. ThedBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fanmanufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-tee requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 3: CAPACITY RATINGS - (ARI 360)1

1. 80/67°F Indoor and 95°F outdoor.

MODEL MBH EER2

2. EER = Energy Efficiency Ratio at full load - the coolingcapacity in Btu’s per hour (Btuh) divided by the powerinput in watts, expressed in Btuh per watt (Btuh/watt).

IPLV3

3. IPLV = Integrated part load value.

COOLING ONLY

D1HE180 177 10.0 10.7

D1HE240 223 9.7 10.2

COOLING WITH GAS HEAT

D1HG180N240 177 10.0 10.7

D1HG180N320 177 10.0 10.7

D1HG240N240 223 9.7 10.2

D1HG240N320 223 9.7 10.2

COOLING WITH ELECTRIC HEAT

D1HE180E018 177 10.0 10.7

D1HE180E036 177 9.9 10.6

D1HE180E054 175 9.7 9.9

D1HE180E072 175 9.7 9.9

D1HE240E018 223 9.6 10.1

D1HE240E036 223 9.6 10.1

D1HE240E054 221 9.5 9.7

D1HE240E072 219 9.5 9.7

TABLE 4: GAS HEAT RATIINGS1

1. All units are two-stage heating. First stage is 50% oftotal.

MODEL MBH INPUT MBH OUTPUT

D1HG180N240 300 240

D1HG180N320 400 320

D1HG240N240 300 240

D1HG240N320 400 320

Page 7: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 7

TABLE 5: COOLING CAPACITIES FOR DHE/DHG 180 AT 85°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

4500

72 16.6 193.2 118.2 192.2 105.1 190.9 92.5 189.1 77.9 186.9 63.3 - - - -

67 16.2 180.7 141.7 179.4 128.8 178.2 114.5 176.9 101.9 175.7 89.1 173.8 74.8 171.5 60.1

62 15.8 176.4 162.3 168.4 150.8 166.0 137.8 164.7 125.0 163.1 111.5 162.0 98.4 160.6 85.6

57 15.6 176.3 162.2 170.6 157.0 165.0 151.8 164.7 125.0 152.5 133.8 150.4 120.7 148.7 107.2

5250

72 16.7 197.5 127.3 196.4 112.1 195.1 97.5 193.2 82.0 190.7 65.0 - - - -

67 16.3 185.9 154.3 184.4 139.1 182.6 122.9 181.2 108.3 179.8 93.7 177.8 78.2 175.2 61.1

62 16.1 185.4 170.6 179.5 165.1 172.1 149.9 169.5 134.7 167.4 119.3 166.3 104.2 164.8 89.6

57 16.0 185.3 170.5 179.4 165.0 173.4 159.5 167.5 154.1 161.5 148.5 155.2 130.1 164.8 89.6

5765

72 16.8 199.9 133.4 198.8 117.0 197.3 100.7 195.3 84.8 192.7 66.2 - - - -

67 16.3 189.8 162.6 187.1 146.0 185.0 128.7 183.5 112.5 182.0 96.6 179.9 80.5 163.2 146.9

62 16.2 190.6 175.3 184.4 169.7 175.3 157.5 172.2 141.2 170.5 125.3 168.5 108.0 167.0 92.1

57 16.1 190.5 175.2 184.3 169.6 178.2 163.9 172.1 158.3 166.0 152.7 158.6 136.6 156.0 120.1

6750

72 16.9 204.7 145.3 202.3 125.5 200.7 106.7 198.6 88.4 195.7 68.3 - - - -

67 16.5 196.3 177.9 191.2 158.3 189.7 139.4 187.1 120.6 185.4 101.8 183.1 83.7 180.0 62.9

62 16.3 198.7 182.8 192.2 176.9 185.7 170.8 177.5 153.3 174.5 134.4 172.1 115.3 170.3 96.6

57 16.2 198.5 182.7 192.1 176.8 185.7 170.8 179.3 164.9 172.9 159.1 163.2 146.9 159.9 128.5

7200

72 16.9 206.2 150.1 203.6 129.3 202.0 109.3 199.8 90.0 196.8 69.3 - - - -

67 16.6 201.9 185.7 194.0 164.5 191.3 143.8 188.4 124.0 186.7 104.1 184.3 85.0 181.1 63.4

62 16.4 201.8 185.6 195.2 179.6 188.7 173.6 179.4 158.0 176.0 138.7 173.4 118.3 171.5 98.6

57 16.3 201.6 185.5 195.1 179.5 188.6 173.5 181.8 167.3 175.3 161.3 166.3 152.0 161.3 132.2

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Page 8: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

8 Unitary Products Group

TABLE 6: COOLING CAPACITIES FOR DHE/DHG 180 AT 95°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

4500

72 17.7 182.9 114.7 181.9 101.4 180.6 88.8 178.8 74.6 176.5 59.9 - - - -

67 17.2 171.3 137.9 170.0 124.9 168.6 110.7 167.3 98.2 165.9 85.3 153.6 141.3 162.0 56.7

62 16.9 168.5 155.1 161.0 146.8 157.0 133.5 155.8 120.9 154.0 107.4 152.9 94.4 151.5 81.5

57 16.7 168.4 155.0 162.9 149.9 157.4 144.8 151.9 139.7 144.3 129.3 142.0 116.4 140.1 103.1

5250

72 17.9 186.9 123.8 185.8 108.5 184.3 93.6 182.4 78.7 179.9 61.6 - - - -

67 17.2 176.8 150.6 174.5 135.3 172.5 118.9 171.2 104.4 169.8 89.8 142.0 116.4 165.4 57.7

62 17.2 176.9 162.8 171.1 157.4 163.0 145.6 160.3 130.7 169.8 89.8 156.8 100.3 155.2 85.4

57 17.0 176.8 162.7 171.0 157.3 165.2 152.0 159.4 146.7 157.9 115.0 147.0 126.2 144.7 110.9

5765

72 18.0 189.8 130.4 187.9 113.1 186.4 96.8 184.4 81.0 181.7 62.8 - - - -

67 17.6 189.8 130.4 177.0 142.1 175.5 125.1 173.3 108.8 171.7 92.6 169.6 76.8 167.1 58.3

62 17.2 181.7 167.2 175.7 161.7 167.3 152.7 162.6 136.7 161.0 121.0 158.9 104.1 157.2 87.9

57 17.1 181.6 167.1 175.6 161.6 169.6 156.1 163.7 150.6 157.7 145.1 158.9 104.1 147.0 115.6

6750

72 18.1 193.5 141.3 191.0 121.6 189.4 102.8 187.3 84.5 184.0 64.8 - - - -

67 17.7 189.3 174.1 181.9 154.8 179.3 135.2 176.5 116.5 174.8 97.7 172.5 79.7 169.7 59.4

62 17.4 189.1 174.0 182.9 168.3 176.7 162.5 167.9 148.7 164.7 130.2 162.1 111.0 160.3 92.4

57 17.3 189.0 173.9 182.8 168.2 176.6 162.4 170.3 156.7 164.1 151.0 158.0 145.3 150.5 124.1

7200

72 18.1 194.9 146.0 192.2 125.4 190.6 105.3 188.4 86.0 185.3 65.9 - - - -

67 17.7 192.1 176.7 183.6 159.8 180.6 139.5 177.7 119.9 175.9 100.0 173.5 80.9 170.1 59.8

62 17.5 192.0 176.6 185.6 170.8 179.3 165.0 170.7 153.7 166.0 134.3 163.2 114.1 161.1 94.1

57 17.4 191.9 176.5 185.5 170.7 179.2 164.9 172.9 159.0 166.5 153.2 160.2 147.4 151.9 127.8

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Nominal Rating

Page 9: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 9

TABLE 7: COOLING CAPACITIES FOR DHE/DHG 180 AT 105°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

4500

72 18.3 144.7 110.9 171.1 97.2 170.0 84.4 168.4 71.2 166.2 56.6 - - - -

67 18.2 161.5 133.9 171.1 97.2 170.0 84.4 157.3 94.2 156.0 81.3 154.4 67.8 138.1 120.7

62 17.8 160.1 147.3 160.1 120.8 148.6 129.3 146.6 116.7 144.7 103.3 143.6 90.2 142.1 77.4

57 17.6 160.0 147.2 154.6 142.3 149.3 137.3 143.9 132.4 138.5 127.4 143.6 90.2 131.2 98.5

5250

72 19.0 175.6 119.6 174.6 104.6 173.3 89.2 170.9 74.9 169.1 58.3 - - - -

67 18.5 166.7 145.5 164.3 131.1 162.9 115.6 160.8 100.5 169.1 58.3 157.5 70.8 154.5 53.9

62 18.1 168.0 154.6 162.2 149.2 156.6 144.0 160.8 100.5 149.0 111.6 147.1 96.0 145.6 81.1

57 17.9 167.9 154.5 162.1 149.1 156.5 143.9 150.6 126.4 145.3 133.7 138.1 120.7 135.6 106.4

5765

72 18.9 178.6 126.3 176.5 109.2 175.1 92.4 172.6 76.9 160.8 148.0 - - - -

67 18.5 170.6 154.0 166.4 137.4 165.1 121.0 162.7 104.7 161.1 88.4 158.4 72.4 156.0 54.5

62 18.2 172.4 158.6 166.6 153.3 160.6 147.8 153.7 132.3 151.2 116.5 148.9 99.7 147.3 83.7

57 18.1 172.3 158.5 166.5 153.2 160.5 147.7 154.7 142.3 148.8 136.9 141.6 127.4 137.7 111.1

6750

72 19.1 181.9 137.0 179.3 117.6 177.7 98.1 175.3 80.7 173.0 61.6 - - - -

67 18.7 179.2 164.9 171.1 149.4 168.4 130.8 165.5 112.3 163.8 93.5 160.9 75.5 158.6 55.7

62 18.5 179.1 164.8 173.1 159.3 167.1 153.8 159.0 143.8 154.4 125.6 151.8 106.7 149.9 88.0

57 18.4 179.0 164.7 173.0 159.2 167.0 153.7 160.8 148.0 154.8 142.4 148.9 136.9 140.9 119.1

7200

72 19.2 183.1 141.7 180.4 121.3 178.7 100.7 176.7 81.5 173.1 62.3 - - - -

67 18.8 181.8 167.3 173.9 155.7 169.6 135.1 166.6 115.7 164.8 95.7 161.8 76.8 159.3 56.2

62 18.6 181.3 166.8 175.3 161.2 169.5 155.9 163.4 150.3 155.7 129.7 152.8 109.7 159.3 56.2

57 18.5 181.2 166.7 175.5 161.5 169.4 155.9 163.3 150.2 157.0 144.4 150.7 138.7 143.0 123.5

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Page 10: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

10 Unitary Products Group

TABLE 8: COOLING CAPACITIES FOR DHE/DHG 180 AT 115°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

4500

72 19.9 161.0 106.8 158.3 145.7 158.8 80.6 157.2 67.7 154.2 52.8 - - - -

67 19.4 151.8 129.4 149.8 116.0 158.8 80.6 157.2 67.7 145.7 76.8 143.9 64.1 140.5 49.0

62 18.8 151.4 139.3 146.2 134.5 139.3 124.8 147.0 89.6 135.6 99.6 134.0 85.5 132.6 72.8

57 18.6 151.4 139.3 146.2 134.5 141.2 129.9 136.0 125.1 130.7 120.3 124.9 108.0 132.6 72.8

5250

72 20.1 164.8 115.7 163.0 100.1 161.7 85.2 160.0 70.8 157.4 54.7 - - - -

67 19.4 157.3 142.4 153.5 126.6 152.2 110.7 150.1 96.3 148.6 81.0 146.7 66.7 143.9 50.3

62 19.1 158.4 145.7 153.0 140.7 147.6 135.8 141.4 121.6 139.0 106.5 137.1 91.8 143.9 50.3

57 18.9 158.3 145.7 152.9 140.7 147.5 135.7 142.2 130.9 136.8 125.8 129.9 116.9 126.2 101.2

5765

72 20.2 166.7 121.4 164.6 104.5 163.3 88.3 161.4 72.6 158.8 55.9 - - - -

67 19.7 162.6 149.6 156.4 133.6 163.3 88.3 151.7 100.4 150.2 83.7 148.0 67.8 144.2 50.5

62 19.3 162.3 149.3 156.8 144.2 163.3 88.3 143.8 127.5 140.9 111.4 138.6 94.8 137.1 78.7

57 19.1 162.2 149.3 156.7 144.2 151.1 139.0 145.5 133.9 140.1 128.9 134.5 123.7 128.1 105.7

6750

72 20.3 169.6 132.0 167.8 113.6 165.6 94.0 163.7 75.9 160.5 57.9 - - - -

67 19.7 168.7 155.2 161.2 145.3 157.1 126.2 154.8 108.1 152.6 88.7 148.9 70.9 145.4 51.4

62 19.5 168.4 154.9 162.7 149.7 156.9 144.4 151.3 139.2 144.6 121.0 141.8 102.1 139.4 82.9

57 19.4 168.3 154.8 162.6 149.6 156.8 144.3 151.1 139.1 145.3 133.7 139.5 128.4 131.9 114.2

7200

72 20.3 170.6 136.6 168.8 117.2 166.5 96.5 164.5 77.4 160.5 58.7 - - - -

67 19.9 170.9 157.3 165.2 151.9 158.9 130.7 164.5 77.4 160.5 58.7 149.6 72.1 143.6 51.0

62 19.6 170.7 157.0 165.1 151.9 159.2 146.5 153.4 141.1 145.9 124.6 142.9 105.0 140.2 84.8

57 19.5 170.6 156.9 165.0 151.8 159.2 146.4 153.3 141.0 147.3 135.5 141.4 130.1 133.2 118.2

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Page 11: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 11

TABLE 9: COOLING CAPACITIES FOR DHE/DHG 240 AT 85°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

6000

72 21.9 247.8 169.2 246.6 149.6 245.2 130.5 243.1 109.8 240.1 88.6 - - - -

67 21.5 232.2 203.8 230.8 184.4 229.5 163.5 228.0 145.2 226.5 126.0 224.3 105.5 221.2 84.2

62 21.1 226.6 226.6 219.6 219.6 214.0 198.6 212.7 179.2 210.9 159.5 209.7 140.2 208.1 121.0

57 20.8 226.5 226.5 219.5 219.5 212.4 212.4 205.4 205.4 197.3 192.7 194.9 173.3 192.9 153.2

7000

72 22.0 252.8 182.7 251.6 160.2 249.8 138.1 247.7 115.6 243.7 90.7 - - - -

67 21.6 238.9 222.6 236.8 200.4 234.8 176.6 233.1 154.7 231.1 132.5 228.9 110.3 220.7 83.6

62 21.3 237.8 237.8 230.4 230.4 221.3 216.3 218.5 194.2 216.8 172.0 214.7 148.9 213.0 126.7

57 21.2 237.7 237.7 230.3 230.3 222.8 222.8 215.5 215.5 208.1 208.1 201.1 187.4 198.9 165.3

8000

72 22.1 257.7 196.6 255.3 170.4 253.6 145.1 251.1 120.5 247.0 93.0 - - - -

67 21.7 245.6 241.5 241.3 215.9 239.7 189.5 236.9 164.0 234.7 138.7 232.3 114.5 217.2 82.4

62 21.5 246.7 246.7 239.0 239.0 231.2 231.2 223.7 208.5 221.1 183.5 218.6 157.5 216.4 132.3

57 21.3 246.6 246.6 238.9 238.9 231.2 231.2 223.5 223.5 215.8 215.8 206.3 200.9 203.2 175.9

9000

72 22.3 261.3 210.1 258.2 180.4 256.4 152.0 252.6 123.4 240.7 92.4 - - - -

67 21.8 254.1 254.1 245.9 230.5 243.2 201.2 239.9 173.4 237.9 144.8 234.9 117.6 - -

62 21.6 254.0 254.0 246.1 246.1 238.1 238.1 228.2 222.7 224.6 194.4 221.6 165.6 219.2 137.4

57 21.5 253.9 253.9 245.9 245.9 238.0 238.0 230.0 230.0 222.1 222.1 214.1 214.1 206.5 185.6

9400

72 22.4 262.5 215.1 259.2 184.4 257.4 154.7 253.4 124.9 248.5 95.7 - - - -

67 21.9 256.7 256.7 247.4 235.9 244.4 205.8 240.9 177.0 238.8 147.1 235.8 118.8 - -

62 21.7 256.6 256.6 248.5 248.5 240.4 240.4 230.9 228.6 225.8 198.7 222.6 168.8 220.2 139.3

57 21.6 256.4 256.4 248.4 248.4 240.4 240.4 232.3 232.3 224.3 224.3 216.2 216.2 207.8 189.6

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Page 12: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

12 Unitary Products Group

TABLE 10: COOLING CAPACITIES FOR DHE/DHG 240 AT 95°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

6000

72 23.5 234.3 164.0 233.1 144.3 231.4 125.3 229.5 105.0 224.1 82.9 - - - -

67 23.1 219.5 197.9 218.2 178.6 216.8 158.0 215.4 139.5 213.8 120.5 211.6 100.5 207.9 79.0

62 22.7 216.3 216.3 209.2 209.2 202.8 192.5 200.8 173.0 199.0 153.8 197.8 134.4 196.1 115.2

57 22.4 216.2 216.2 209.4 209.4 202.5 202.5 195.6 195.6 188.6 188.6 183.6 166.8 181.7 147.3

7000

72 23.6 239.6 178.5 237.5 154.8 235.9 132.6 233.6 110.8 229.0 85.7 - - - -

67 23.2 226.1 216.7 223.7 194.8 222.4 171.7 219.9 149.1 217.9 126.9 215.6 105.2 202.3 76.7

62 22.9 226.6 226.6 219.4 219.4 212.1 212.1 206.1 187.9 204.5 165.7 202.4 142.9 200.5 120.9

57 22.7 226.5 226.5 219.3 219.3 212.1 212.1 204.9 204.9 197.6 197.6 189.7 181.0 187.2 158.7

8000

72 23.7 243.3 191.1 240.9 165.0 239.2 139.6 236.6 115.0 230.0 87.4 - - - -

67 23.4 234.9 234.9 240.9 165.0 226.3 183.8 223.3 158.3 221.5 133.1 217.7 108.2 215.9 82.0

62 23.1 234.8 234.8 227.2 227.2 219.8 219.8 211.4 202.2 208.4 176.9 205.8 151.2 203.8 126.1

57 22.9 234.7 234.7 227.1 227.1 219.6 219.6 212.3 212.3 204.8 204.8 197.2 197.2 191.1 169.0

9000

72 23.8 246.7 204.4 243.5 174.9 241.6 146.4 237.6 117.6 237.9 91.6 - - - -

67 23.5 241.6 241.6 232.3 224.0 229.2 194.9 226.0 167.3 224.0 139.0 220.8 111.6 209.5 79.8

62 23.2 241.5 241.5 233.8 233.8 226.1 226.1 218.4 218.4 211.5 187.7 208.5 159.2 206.3 131.1

57 23.1 241.3 241.3 233.7 233.7 225.8 225.8 218.1 218.1 210.4 210.4 202.8 202.8 194.3 179.2

9400

72 23.9 247.4 208.8 245.2 179.6 242.5 149.1 238.2 119.1 230.7 89.8 - - - -

67 23.6 243.9 243.9 234.8 230.5 230.3 199.4 227.7 171.5 224.8 141.3 221.5 112.7 - -

62 23.3 243.8 243.8 236.0 236.0 228.3 228.3 220.5 220.5 212.7 192.2 210.2 163.0 207.1 133.0

57 23.2 243.7 243.7 235.9 235.9 228.0 228.0 220.2 220.2 212.4 212.4 204.7 204.7 196.1 183.3

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Nominal Rating

Page 13: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 13

TABLE 11: COOLING CAPACITIES FOR DHE/DHG 240 AT 105°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

6000

72 25.1 220.4 158.8 219.1 138.9 217.6 119.8 215.4 100.1 209.0 77.7 - - - -

67 24.5 207.2 192.5 205.4 173.0 203.8 152.5 202.3 133.9 200.7 114.9 198.3 95.3 193.8 73.5

62 24.0 205.6 205.6 198.9 198.9 191.0 186.5 188.7 167.2 187.2 148.1 185.5 128.4 183.8 109.4

57 23.7 205.5 205.5 198.8 198.8 192.1 192.1 185.4 185.4 178.4 178.4 172.2 160.8 170.7 141.6

7000

72 25.2 225.1 172.3 223.0 149.3 221.4 127.0 219.0 105.4 213.8 80.6 - - - -

67 24.6 214.0 211.5 210.3 189.1 208.8 165.4 206.4 143.4 204.4 120.2 201.9 99.8 199.4 75.6

62 24.3 215.0 215.0 208.1 208.1 201.1 201.1 194.3 182.2 191.9 159.7 189.6 137.0 187.1 114.4

57 24.1 214.9 214.9 208.0 208.0 201.0 201.0 193.9 193.9 186.9 186.9 178.1 174.5 175.3 152.4

8000

72 25.4 228.5 185.3 226.0 159.4 224.2 134.0 221.6 109.3 218.8 79.6 - - - -

67 24.9 222.5 222.5 214.9 203.8 212.5 177.9 209.4 152.5 207.5 127.3 203.5 102.3 - -

62 24.5 222.4 222.4 215.2 215.2 208.0 208.0 199.6 196.6 195.4 170.8 192.5 145.2 189.9 119.8

57 24.4 222.3 222.3 215.1 215.1 208.0 208.0 200.7 200.7 193.4 193.4 186.0 186.0 178.8 163.0

9000

72 25.5 231.2 198.0 229.1 169.8 226.4 140.7 223.5 113.1 219.6 81.7 - - - -

67 25.0 228.3 228.3 219.6 217.8 215.1 188.8 212.6 161.9 209.7 133.0 205.9 105.8 - -

62 24.7 228.2 228.2 220.8 220.8 213.7 213.7 206.2 206.2 199.0 182.0 195.6 153.5 192.7 124.8

57 24.5 228.1 228.1 220.7 220.7 213.6 213.6 206.1 206.1 198.6 198.6 191.0 191.0 182.5 172.5

9400

72 25.6 232.2 203.0 230.0 173.6 227.2 143.3 224.2 114.5 183.7 72.1 - - - -

67 25.1 230.4 230.4 223.1 223.1 216.0 193.2 213.5 165.3 210.5 135.2 206.9 106.6 - -

62 24.8 230.3 230.3 222.9 222.9 215.6 215.6 208.1 208.1 200.1 185.9 196.5 156.4 193.5 126.7

57 24.6 230.1 230.1 222.8 222.8 215.3 215.3 208.0 208.0 200.4 200.4 192.8 192.8 183.6 176.0

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Page 14: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

14 Unitary Products Group

TABLE 12: COOLING CAPACITIES FOR DHE/DHG 240 AT 115°FAir On Evaporator

CoilCapacity (MBH) at Entering Dry Bulb (°F)

86 83 80 77 74 71 68

CFM WB °FTot.1

Input(kW)

TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN TOT2 SEN

6000

72 26.5 206.3 153.2 204.4 132.6 203.2 114.2 199.3 94.3 192.0 71.9 - - - -

67 25.8 194.2 186.8 192.1 167.5 190.9 147.2 188.9 128.2 187.2 109.1 184.6 90.1 178.8 178.8

62 25.4 194.1 194.1 187.6 187.6 181.4 181.4 176.2 161.3 187.2 109.1 172.9 122.4 171.1 103.4

57 24.9 194.0 194.0 187.6 187.6 181.1 181.1 174.5 174.5 167.9 167.9 161.1 154.8 158.9 135.4

7000

72 26.6 210.3 166.6 207.7 142.9 205.6 120.4 203.9 99.6 203.6 77.1 - - - -

67 26.1 202.9 202.9 197.0 183.2 195.0 159.4 192.4 137.5 190.6 115.3 187.6 93.6 - -

62 25.6 202.8 202.8 196.1 196.1 189.2 189.2 181.6 175.7 178.9 153.5 176.5 130.8 173.6 108.1

57 25.4 202.7 202.7 196.0 196.0 189.3 189.3 182.5 182.5 175.7 175.7 168.5 168.5 163.0 146.0

8000

72 26.7 213.4 179.5 211.3 154.3 208.9 128.1 206.0 103.0 202.7 77.4 - - - -

67 26.3 209.5 209.5 201.7 198.1 198.1 171.2 195.8 147.1 193.1 121.2 187.9 96.1 147.9 57.4

62 25.9 209.4 209.4 202.6 202.6 195.5 195.5 195.8 147.1 182.1 164.4 179.9 139.4 176.9 113.6

57 25.7 209.3 209.3 202.5 202.5 195.6 195.6 188.6 188.6 181.5 181.5 174.2 174.2 166.9 156.4

9000

72 26.8 216.3 192.6 213.6 163.7 210.8 134.7 207.5 106.3 203.7 77.6 - - - -

67 26.5 214.7 214.7 207.8 207.8 201.3 183.1 198.1 155.6 195.0 126.8 190.2 98.8 - -

62 26.1 214.6 214.6 207.7 207.7 200.6 200.6 193.5 193.5 185.5 175.4 182.2 146.9 178.8 118.3

57 26.0 214.5 214.5 207.6 207.6 200.6 200.6 193.4 193.4 186.2 186.2 178.8 178.8 170.6 166.6

9400

72 26.9 217.7 198.2 214.4 167.4 211.4 137.3 207.9 107.6 204.6 77.8 - - - -

67 26.6 216.6 216.6 209.6 209.6 202.3 187.2 198.9 158.9 195.7 128.9 187.8 96.9 - -

62 26.2 216.4 216.4 209.5 209.5 202.4 202.4 195.2 195.2 186.6 178.8 183.0 149.8 179.5 120.1

57 26.1 216.4 216.4 209.4 209.4 202.3 202.3 195.1 195.1 187.8 187.8 180.4 180.4 171.9 170.6

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to

the appropriate Blower Performance Table for the kW of the supply air blower motor.

Page 15: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 15

TABLE 13: DHG 15 TON SUPPLY AIR BLOWER PERFORMANCE

DHG180 - BOTTOM DUCT CONNECTIONS1, 2

BLOWERSPEED,(RPM)

MOTORPULLEY(TURNS

OPEN)3

CFM

4500 5250 6000 6750 7200

ESP4 BHP KW ESP3 BHP KW ESP3 BHP KW ESP3 BHP KW ESP3 BHP KW

208 VOLT AND STANDARD DRIVE

850 6.05 0.9 2.4 2.1 0.6 2.9 2.6 0.3 3.4 3.0 - - - - - -

870 5.5 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 - - - - - -

915 4.5 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -

965 3.5 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5

980 3.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1010 2.0 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8

1040 1.0 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

965 6.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5

980 5.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1025 4.5 1.4 3.1 2.8 1.2 3.6 3.2 0.9 4.1 3.7 0.7 4.8 4.3 0.4 5.5 4.9

1065 3.5 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -

1125 2.0 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - -

1170 1.0 2.1 3.9 3.5 1.9 4.7 4.2 1.6 5.5 4.9 - - - - - -

230/460 VOLT AND STANDARD DRIVE

870 6.04 1.0 2.5 2.2 0.7 3.0 2.7 0.4 3.5 3.1 - - - - - -

915 5.0 1.1 2.6 2.4 0.8 3.1 2.8 0.5 3.6 3.2 0.2 4.1 3.7 - - -

965 4.0 1.2 2.7 2.5 0.9 3.2 2.9 0.6 3.7 3.3 0.4 4.4 3.9 0.2 5.0 4.5

980 3.5 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1015 2.5 1.4 3.0 2.7 1.1 3.6 3.2 0.8 4.0 3.6 0.6 4.7 4.2 0.4 5.4 4.8

1050 1.5 1.5 3.1 2.8 1.2 3.7 3.3 0.9 4.2 3.8 0.7 4.9 4.4 0.5 5.7 5.1

1065 1.0 1.6 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -

230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY

980 6.0 1.3 2.9 2.6 1.0 3.4 3.0 0.7 3.8 3.4 0.5 4.5 4.0 0.3 5.1 4.6

1045 4.5 1.6 3.2 2.9 1.3 3.8 3.4 1.0 4.4 3.9 0.8 5.0 4.5 0.6 5.6 5.0

1065 4.0 1.7 3.4 3.0 1.4 3.9 3.5 1.1 4.5 4.0 0.9 5.1 4.6 - - -

1125 2.5 1.9 3.6 3.2 1.7 4.4 3.9 1.4 5.0 4.5 1.2 5.8 5.2 - - -

1170 1.5 2.1 3.9 3.5 1.8 4.7 4.2 1.6 5.5 4.9 - - - - - -

1190 1.0 2.2 4.0 3.6 1.9 4.8 4.3 1.7 5.6 5.0 - - - - - -

1. Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.2. Refer to the Static Resistance table.3. DO NOT close the pulley below one turn open.4. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been

deducted from the total static pressure of the blower.5. The factory setting.

Page 16: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

16 Unitary Products Group

TABLE 14: DHG 20 TON SUPPLY AIR BLOWER PERFORMANCE

DHG240 - BOTTOM DUCT CONNECTIONS1, 2

BLOWERSPEED,(RPM)

MOTORPULLEY(TURNS

OPEN)3

CFM

6000 7000 8000 9000 9400

ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW

208 VOLT AND STANDARED DRIVE

870 6.05 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - - - -

900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - - - -

930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -

950 3.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

980 2.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 1.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1015 1.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.7 7.8 6.6 - - -

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -

1050 2.5 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - -

1065 2.0 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - -

1100 1.0 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - - - - -

230/460 VOLT AND STANDARD DRIVE

870 6.05 1.3 3.6 3.0 0.7 4.3 3.7 0.2 5.1 4.3 - - - - - -

900 5.0 1.4 3.8 3.2 0.9 4.7 4.0 0.4 5.6 4.7 - - - - - -

930 4.0 1.6 4.1 3.4 1.1 5.0 4.2 0.6 5.9 5.0 0.1 6.7 5.7 - - -

950 3.5 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

965 2.5 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 2.0 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1015 1.5 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - -

1025 1.0 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -

230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY

950 6.0 1.7 4.2 3.6 1.3 5.1 4.3 0.8 6.0 5.1 0.2 6.9 5.8 - - -

980 5.0 1.9 4.5 3.8 1.5 5.4 4.5 1.0 6.3 5.3 0.4 7.2 6.1 0.1 8.5 7.1

995 4.5 2.1 4.6 3.9 1.6 5.5 4.7 1.1 6.4 5.4 0.5 7.5 6.3 0.2 8.6 7.3

1015 4.0 2.2 4.8 4.0 1.7 5.7 4.8 1.2 6.6 5.6 0.6 7.8 6.6 - - -

1025 3.5 2.3 4.9 4.1 1.8 5.8 4.9 1.3 6.7 5.7 0.7 8.0 6.7 - - -

1050 3.0 2.5 5.1 4.3 2.0 6.1 5.1 1.4 7.1 6.0 0.9 8.4 7.0 - - -

1065 2.5 2.6 5.3 4.4 2.1 6.3 5.3 1.5 7.3 6.2 1.0 8.6 7.2 - - -

1100 1.5 2.9 5.6 4.7 2.3 6.8 5.7 1.8 7.9 6.6 - - - - - -

1120 1.0 3.1 5.8 4.9 2.5 7.0 5.9 1.9 8.3 6.9 - - - - - -

1. Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.2. Refer to the Static Resistance table.3. DO NOT close the pulley below one turn open.4. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have

been deducted from the total static pressure of the blower.5. The Factory Setting.

Page 17: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 17

TABLE 15: DHE 15 TON SUPPLY AIR BLOWER PERFORMANCE

DHE180 - BOTTOM DUCT CONNECTIONS1, 2

BLOWERSPEED,(RPM)

MOTORPULLEY(TURNS

OPEN)3

CFM

4500 5250 6000 6750 7200

ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW

208 VOLT AND STANDARD DRIVE

850 6.05 0.9 2.4 2.2 0.7 3.0 2.7 0.5 3.2 2.9 - - - - - -

870 5.5 1.0 2.5 2.3 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -

915 4.5 1.1 2.6 2.4 0.9 3.4 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0

965 3.5 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 4.9 4.4

980 3.0 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1010 2.0 1.4 3.1 2.8 1.2 3.8 3.4 1.0 4.2 3.8 0.7 5.0 4.5 0.6 5.4 4.8

1040 1.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.2 4.7 0.7 5.7 5.1

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

965 6.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4

980 5.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1025 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.8 5.1 4.6 0.7 5.6 5.0

1065 3.5 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -

1095 3.0 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - -

1130 2.0 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 - - - - - -

1170 1.0 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 - - - - - -

230/460/575 VOLT AND STANDARD DRIVE

870 6.05 1.0 2.4 2.2 0.8 3.1 2.8 0.6 3.5 3.1 0.2 4.1 3.7 - - -

915 5.0 1.1 2.6 2.4 0.9 3.3 3.0 0.7 3.7 3.3 0.3 4.4 3.9 0.2 4.5 4.0

965 4.0 1.2 2.9 2.6 1.0 3.6 3.2 0.8 4.0 3.6 0.5 4.7 4.2 0.4 5.0 4.4

980 3.5 1.3 3.0 2.7 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1040 2.0 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1

1065 1.0 1.6 3.3 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY

980 6.0 1.3 2.9 2.6 1.1 3.7 3.3 0.9 4.1 3.7 0.6 4.8 4.3 0.5 5.1 4.6

1040 4.5 1.5 3.2 2.9 1.3 3.9 3.5 1.1 4.5 4.0 0.9 5.3 4.7 0.7 5.7 5.1

1065 4.0 1.6 3.4 3.0 1.4 4.0 3.6 1.2 4.7 4.2 1.0 5.5 4.9 - - -

1095 3.5 1.7 3.5 3.1 1.5 4.2 3.8 1.3 4.9 4.4 1.2 5.7 5.1 - - -

1130 2.5 1.9 3.7 3.3 1.7 4.5 4.0 1.5 5.1 4.6 - - - - - -

1170 1.5 2.1 3.9 3.5 2.0 4.7 4.2 1.8 5.5 4.9 - - - - - -

1190 1.0 2.2 4.0 3.6 2.1 4.8 4.3 2.0 5.7 5.1 - - - - - -

1. Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.2. Refer to the Static Resistance table.3. DO NOT close the pulley below one turn open.4. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been

deducted from the total static pressure of the blower.5. The Factory Setting.

Page 18: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

18 Unitary Products Group

TABLE 16: DHE 20 TON SUPPLY AIR BLOWER PERFORMANCE

DHE240 - BOTTOM DUCT CONNECTIONS1, 2

BLOWERSPEED,(RPM)

MOTORPULLEY(TURNS

OPEN)3

CFM

600 7000 8000 9000 9400

ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW ESP4 BHP KW

208 VOLT AND STANDARD DRIVE

870 6.05 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - - - -

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - -

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -

950 3.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 2.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1015 1.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1010 4.0 1.8 5.8 4.9 1.7 6.3 5.3 1.5 6.9 5.8 1.0 7.5 6.3 0.5 7.9 6.7

1020 3.5 1.9 6.1 5.1 1.8 6.5 5.5 1.6 7.1 6.0 1.1 7.8 6.6 0.6 8.3 7.0

1035 3.0 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3

1050 2.5 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -

1075 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -

1100 1.0 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - -

230/460/575 VOLT AND STANDARD DRIVE

870 6.05 0.4 2.1 1.8 0.1 2.3 2.0 - - - - - - - - -

900 5.0 0.8 3.2 2.7 0.5 3.5 2.9 0.2 3.8 3.2 - - - - - -

930 4.0 1.1 4.1 3.4 0.9 4.5 3.8 0.6 4.9 4.1 0.1 5.1 4.3 - - -

950 3.5 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 2.5 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1015 1.5 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9

1025 1.0 2.0 6.1 5.1 1.8 6.6 5.6 1.6 7.3 6.1 1.1 7.9 6.7 0.7 8.6 7.3

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY

950 6.0 1.3 4.6 3.9 1.1 5.1 4.3 0.8 5.5 4.6 0.4 5.9 5.0 - - -

980 5.0 1.6 5.3 4.5 1.4 5.8 4.9 1.2 6.3 5.3 0.7 6.9 5.8 0.2 7.3 6.1

1015 4.0 1.9 5.9 5.0 1.7 6.5 5.5 1.5 7.0 5.9 1.0 7.7 6.5 0.6 8.2 6.9

1035 3.5 2.0 6.2 5.2 1.9 6.8 5.7 1.7 7.4 6.2 1.2 8.1 6.8 0.7 8.6 7.3

1050 3.0 2.1 6.4 5.4 2.0 7.0 5.9 1.8 7.6 6.4 1.3 8.3 7.0 - - -

1080 2.0 2.3 6.6 5.5 2.1 7.2 6.0 1.9 7.8 6.6 1.5 8.6 7.2 - - -

1100 1.5 2.4 6.7 5.6 2.2 7.3 6.1 2.1 7.9 6.7 - - - - - -

1120 1.0 2.5 6.8 5.7 2.3 7.4 6.2 2.2 8.1 6.8 - - - - - -

1. Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.2. Refer to the Static Resistance table.3. DO NOT close the pulley below one turn open.4. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been

deducted from the total static pressure of the blower.5. The Factory Setting.

Page 19: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 19

TABLE 17: BLOWER MOTOR AND DRIVE DATA (DHG/DHE MODELS)

MODELSIZE

DRIVEBLWR

RANGE(RPM)

MOTOR1 ADJ. MOTOR PULLEY FIXED BLOWER PULLEYBELT

(NOTCHED)

HP FRAMEEFF.(%)

DESIGN-NATION

O/D(in.)

PITCHDIA(in.)

BORE(in.)

DESIGN-NATION

O/D(in.)

PITCHDIA(in.)

BORE(in.)

DESIG-NATION

PITCHLNGTH.

(in.)QTY.

15 Ton

Std. 850/1065

5 184T 89.5 1VP56 5.354.3-

5.32 1-1/8

BK90 8.75 8.4 1 BX70 71.8 1

HighSpd.Acs.

965/1190 BK80 7.75 7.4 1 BX68 69.8 1

20 Ton

Std. 870/1025

7.5 213T 91 1VP68 6.755.5-

6.52 1-3/8

BK120 11.75 11.4 1-3/16 BX83 84.8 1

HighSpd.Acs.

950/1120 BK110 10.75 10.4 1-3/16 BX80 81.8 1

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base.2. DO NOT close this pulley below 1 turn.

TABLE 18: STATIC RESISTANCES1

DESCRIPTION

RESISTANCE, IWG

CFM

15 TON 20 TON

4500 5765 7200 6000 7000 9400

WET COIL 0.1 0.1 0.1 0.1 0.1 0.1

ELECTRIC HEATOPTIONS(DHE models only)

18kW 0.1 0.1 0.1 0.1 0.1 0.1

36kW 0.1 0.2 0.3 0.1 0.2 0.3

54kW 0.2 0.3 0.4 0.2 0.3 0.4

72kW 0.2 0.4 0.6 0.2 0.4 0.6

EXONOMIZER OPTION 0.1 0.1 0.1 0.1 0.1 0.1

HORIZONTAL DUCT CONN.2 0.2 0.3 0.5 0.2 0.3 0.5

1. Deduct theses resistance values from the available unit ESP values listed in the respective blower per-formance table except for Horizontal Duct Connections.

2. Add these values due to less airflow resistance.

TABLE 19: POWER EXHAUST PERFORMANCE

MOTOR

SPEED1

STATIC RESISTANCE OF RETRUN DUCTWORK, IWG

0.2 0.3 0.4 0.5 0.6

CFM kW CFM kW CFM kW CFM kW CFM kW

HIGH2 5250 0.83 4500 0.85 4200 0.88 3750 0.93 3000 0.99

MEDIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - -

LOW 4400 0.72 3700 0.74 3000 0.78 - - - -

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.2. The factory setting.

Page 20: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

20 Unitary Products Group

TABLE 20: DHG ELECTRICAL DATA

MODELPOWERSUPPLY

COMPRESSORS COND. FANMOTORS(#1 & #2)

SUPPLY AIRBLOWERMOTOR

MIN.CIRCUIT

AMPACITY(AMPS)

MAX. TIMEDELAY FUSESIZE (AMPS)

MIN. WIRE

SIZE1#1 #2

RLA LRA RLA LRAHP

(ea.)FLA(ea.)

HP FLA 75°C

DHG180208/230-3-60 28.6 274 14.3 137 1 4.1/4.2 5 11.8 77.8/77.0 90 4

460-3-60 14.4 138 7.2 69 1 2.1 5 5.9 42.7 50 8

DHG240208/230-3-60 28.6 274 28.6 274 1 4.1/4.2 7.5 18.6 98.6/96.8 110 3

460-3-60 14.4 138 14.4 138 11 2.1 7.5 9.3 52.2 60 6

1. Although these sizes are based on copper conductors aluminum wire can be use3d. Refer to the National Electric Code to deter-mine the proper size

TABLE 21: DHG VOLTAGE LIMITATIONS1

1. Utilization Range “A” in accordance with ARI Standard110.

POWER SUPPLY VOLTAGE

MIN. MAX.

208/230-3-60 187 253

460-3-60 414 506

TABLE 22: DHE VOLTAGE LIMITATIONS1

1. Utilization Range “A” in accordance with ARI Standard110.

POWER SUPPLY VOLTAGE

MIN. MAX.

208/230-3-60 187 253

460-3-60 414 506

575-3-60 518 506

TABLE 23: DHE ELECTRICAL DATA

MODELPOWERSUPPLY

COMPRESSORS COND. FANMOTORS(#1 & #2)

SUPPLY AIRBLOWERMOTOR

MIN.CIRCUIT

AMPACITY(AMPS)

MAX. TIMEDELAY FUSESIZE (AMPS)

MIN. WIRE

SIZE1#1 #2

RLA LRA RLA LRAHP

(ea.)FLA(ea.)

HP FLA 75°C

DHE180

208/230-3-60 28.6 274 14.3 137 1 3.6 5 11.8 77.0 90 4

460-3-60 14.4 138 7.2 69 1 2.0 5 5.9 42.7 50 8

575-3-60 11.4 116 5.7 58 1 1.4 5 5.2 30.7 35 8

DHE240

208/230-3-60 28.6 274 28.6 274 1 3.6 7.5 18.6 98.6 110 3

460-3-60 14.4 138 14.4 138 1 2.0 7.5 9.3 52.2 60 6

575-3-60 11.4 116 11.4 116 1 1.4 7.5 7.5 40.2 45 8

1. Although these sizes are based on copper conductors aluminum wire can be used. Refer to the National Electric Code to deter-mine the proper size.

Page 21: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 21

TABLE 24: ELECTRICAL DATA UNITS WITH SUPPLEMENTAL ELECTRIC HEAT

MODELD1HE

POWERSUPPLY

HEATER OPTION MIN. CIRCUITAMPACITY

(AMPS)

MAX. TIMEDELAY FUSESIZE (AMPS)MODEL kW1 STAGES AMPS

180A25

208-3-60

E018 13.5 1 37.5 77.0 90

E036 27.0 2 75.1 111.8 125

E054 40.6 2 112.6 158.7 175

E072 54.1 2 150.1 168.1 200

230-3-60

E018 18.0 1 43.3 77.0 90

E036 36.0 2 86.6 126.3 150

E054 54.0 2 129.9 147.9 175

E072 72.0 2 173.2 191.2 225

180A46 460-3-60

E018 18.0 1 21.7 42.7 50

E036 36.0 2 43.3 63.1 70

E054 54.0 2 65.0 74.0 90

E072 72.0 2 86.6 95.6 110

180A58 575-3-60

E018 18.0 1 17.3 30.7 35

E036 36.0 2 34.6 50.7 60

E054 54.0 2 52.0 59.3 70

E072 72.0 2 69.3 76.7 90

240A25

208-3-60

E018 13.5 1 37.5 96.8 110

E036 27.0 2 75.1 118.1 125

E054 40.6 2 112.6 165.0 175

E072 54.1 2 150.1 174.4 200

230-3-60

E018 18.0 1 43.3 96.8 110

E036 36.0 2 86.6 132.5 150

E054 54.0 2 129.9 154.2 175

E072 72.0 2 173.2 197.5 225

240A46 460-3-60

E018 18.0 1 21.7 52.2 60

E036 36.0 2 43.3 66.3 70

E054 54.0 2 65.0 77.1 90

E072 72.0 2 86.6 98.7 110

240A58 575-3-60

E018 18.0 1 17.3 40.2 45

E036 36.0 2 34.6 53.1 60

E054 54.0 2 52.0 61.7 70

E072 72.0 2 69.3 79.0 90

1. See Table 25 for electric heat correction factors.

TABLE 25: ELECTRIC HEAT CORRECTION FACTORSNOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER

208 208 1.00

240 230 0.92

480 460 0.92

600 575 0.92

Page 22: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

22 Unitary Products Group

FIGURE 2 : DHG/DHE FIELD WIRING DIAGRAM

��

��

��

��

��

��

���

��

��

����

���

���

� ���

��

� �

����

��

��

��

��

��

��

��

��

���

�����

��

� ������

� ���� ������� ����� ���������������

������ !"#��$ !% &''&(����)� '!*�&��������������+#"��,-�*�*,((&*�./���� '#"&��(�!�0���1��!�&��-�!"� ��&2�(!& -�#"���13!���*���#!"�!4��)��,"#���!"� !��(!5/�����!"-�*�&%��)�&�#"%�#*�"!�� �6,# �-�!"�,"#�*�7#�)�&�*#"%���*�&%������� #��)�&�� /���� '#"&�*����&"-����$ !3#-��&� ��&2�!,�$,���!���!*���)��!,�-!! ���!"!'#8� �-&'$� *���7)�"��)���)� '!*�&��*7#��)�*��!��)��*��1(&�0�$!*#�#!"/������������ ����� �������������� ���������������� ��� ������������ �������� ���

����9 ������������� �:�������� ��� � �

�� ������

��4� ��!��)�����������������&(��*��!�*#8���)��$!7� �7# #"%;��)���4,*�*�&"-��)��-#*�!""����*7#��)/

���9 �������� ����

� ����<���������+���9 ������� ����.

����� ��������������

�����������

������������� �:����

����9!����)� '!*�&��������������! ���������=�����+7#�)��,((&*������������./���� '#"&��*� #$����1��!�&��-�!"� ��&2�(!& -�#"���13!���*���#!"����!4��)��,"#���!"� !��(!5/������!"-�*�&%��)�&�#"%�#*�"!�� �6,# �-�!"�,"#�*�7#�)�&�*#"%���*�&%��������� #��)�&�� /

����� ��������������

������������� �:�����

� ���� ���+���9 ������� ����.

���9 �������� ����

����������

����>��?��

����>��?��

����>��?��

TABLE 26: PHYSICAL DATA

MODELSDHG/DHE

180 240

EVAPORATORBLOWER

Centrifugal Blower (Dia. x Wd. in.) 15 x 15 18 x 15

Fan Motor HP 5 7.5

EVAPORATORCOIL

Rows Deep 4 4

Fins Per Inch 13.5 13.5

Face Area (Sq. Ft. 15.5 20.0

CONDENSERFANS

(Two Per Unit)

Propeller Dia. (in.) (Each) 30 30

Fan Motor Hp (Each) 1 1

Nom. CFM (Each) 5765 7000

CONDENSERCOILS

(Two Per Unit)

Rows Deep (Each) 3 3

Fins Per Inch (Each) 13 15

Face Area (Sq. Ft.) (Total) 36.0 43.3

COMPRESSOR(Qty. Per Unit)

10-Ton Tandem Hermetic Recip. 11

1. This compressor will be energized first.

2

5-Ton Hermetic Recip. 1 -

AIRFILTERS

Quantity Per Unit (16” X 20” X 2”) - 4

Quantity Per Unit (16” X 25” X 2”) - 4

Quantity Per Unit (18” X 24” X 2”) 5 -

Total Face Area (sq. ft.) 15.0 20.0

CHARGERefrigerant 22

(lbs./oz.)

System #1 29/9 23

System #2 14/8 23/12

TABLE 27: OPERATING WEIGHTS (LBS.)MODEL SIZE 15 TON 20 TON

BASICUNIT

DHE (Cooling Only) 1900 2100

DHG(Gas/Electric)

240Mbh 2100 2300

320Mbh 2140 2340

OPTIONS

Economizer 160

Economizer withPower Exhaust

245

Motorized Damper 150

Electric Heater(DHE only)

18kW 25

36kW 30

54kW 35

72kW 40

ACCY.

Roof Curb 175 185

Barometric Damper 45 45

Wood Skid 220 220

Page 23: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 23

NOTE: A 1” clearance must be provided between any com-bustible material and the supply air ductwork for a distance of3 feet from the unit.

NOTE: The products of combustion must not be allowed toaccumulate within a confined space and recirculate.

NOTE: Locate unit so that the vent air outlet hood is at least:

• Three (3) feet above any force air inlet located within 10horizontal feet (excluding those integral to the unit).

• Four (4) feet below, 4 horizontal feet from, or 1 footabove any door or gravity air inlet into the building.

• Four (4) feet from electric and gas meters, regulatorsand relief equipment

NOTE: All entry holes should be field sealed to prevent rainwater entry into building.

FIGURE 3 : UNIT DIMENSIONS DHE/DHG180 & 240 (FRONT VIEW)

RETURNAIR

SUPPLYAIR

BOTTOM SUPPLYAND RETURNAIR OPENINGS

(See Note)

(B)POWER WIRINGENTRY

(A)CONTROL WIRINGENTRY

NOTE:For curb mounted units, refer to the curb hangerdimensions of the curb for the proper size of thesupply and return air duct connections.

UNIT BASE WITH RAILS

Shown separately to illustrateBottom Duct openings, Powerand Gas Piping Connectionlocations

12-1/2"

9-1/4"

8-1/8"

9-3/4"

3-3/4"

(B)POWER WIRINGENTRY

(A)CONTROL WIRINGENTRY

CONDENSERCOILS

OPTIONAL COILGUARD KIT

COMPRESSORACCESS(See detail "X")

ECONOMIZER / MOTORIZED DAMPER,FIXED OUTDOOR INTAKE AIR ANDPOWER EXHAUST RAIN HOODS(See detail "Y")

FIELD-SUPPLIEDDISCONNECT SWITCHLOCATION

BLOWERACCESS

BLOWER MOTORACCESS

BLOWERCOMPARTMENTACCESS(Auxiliary)

DOT PLUG(For pressureDrop Reading)

FRONTVIEW

CONTROL BOXACCESS

21"

5"

9-3/4"

11-1/2"

2-3/4" 21-1/2"

33"

35"

5-7/8"

46-5/8"

7-1/8"

6-3/8"

VENT AIROUTLETHOODS

COMBUSTIONAIR INLETHOOD

GAS HEATACCESS

(C)GAS SUPPLYENTRY

46-5/8"

11-1/8"

(D)GAS SUPPLYENTRY

RETURN AIR

SUPPLY AIR

OUTDOOR AIR

OUTDOOR AIR(Economizer)

92"

24-1/4" (15Ton)

35-1/4" (20Ton)

125-1/4"(15Ton)

136-1/4"(20Ton)

48-5/8" (15 Ton)52-5/8" (20 Ton)

All dimensions are in inches. They aresubject to change without notice. Certi-fied dimensions will be provided uponrequest.

TABLE 28: MINIMUM CLEARANCESLOCATION CLEARNANCE

Front 36”

Back24” (Less Economizer)49” (With Economizer

Left Side (Filter Access)24” (Less Economizer)36” (With Economizer)

Right Side (Cond. Coil) 36”

Below Unit1 0”

Above Unit272” With 36” Maximum

Horizontal Overhang (ForCondenser Air Discharge)

1. Units may be installed on combustible floors madefrom wood or class A, B, or C roof covering material.

2. Units must be installed outdoors. Overhanging struc-tures or shrubs should not obstruct condenser air dis-charge outlet.

TABLE 29: UTILITIES ENTRYHOLE OPENING SIZE (DIA.) USED FOR

A1-1/8” KO

Control WiringFront

3/4” NPS (Fem.) Bottom

B3-5/8” KO

Power WiringFront

3” NPS (Fem.) Bottom

C 2-3/8” KO Gas Piping (Front)1

D 1-11/16” Hole Gas Pipping (Bottom)1,2

1. One-inch Gas Piping MPT Required.2. Opening in the bottom to the unit can be located by the

side in the insulation.

Page 24: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

24 Unitary Products Group

NOTE: Units are shipped with the bottom duct openings ocov-ered. An accessory flange kit is available for connecting sideducts.

For bottom duct applications:

1. Remove the side panels from the supply and return aircompartments to gain access to the bottom supply andreturn air duct covers.

2.Remove and discard the bottom duct covers. Ductopenings are closed with sheet metal covers exceptwhen the unit includes a power exhaust option. Thecovering consists of a heavy black paper composi-tion.

3.Replace the side supply and return air compartmentpanels.

For side duct application:

1. Replace the side panels on the supply and return aircompartments with the accessory flange kit panels.

2.Connect ductwork to the duct flanges on the rear ofthe unit.

FIGURE 4 : UNIT DIMENSIONS DHE/DHG180 & 240 (REAR VIEW)

� � � � � �

� � �

� � � � � �

� � �

� � � �

� � �

� � � � � � � � � �

� � � �

� � � � � � � �

� � � �

� � � � � � � �

� � � �

� � � � � � � � � � � � � �

� � � � � � � � � �

� � � �

� � � � � � � � � �

� � � � � � � � � � �

� � � �

� � � � � � � � � � � � �

� � � � � � � � �

� � � � � � � � � �

� � � � � �

� � � �

� � � � � � �

� � � � � � � � � � � � �

� � � � � � � � � � ! "

� # � � � � � � � �

� � � � � �

$ % & � ' ( �

( ) & * ' ) � � � � * � � � � "

+ , & * ' ) � � � ( % � � � � "

( - & + ' $ �

* & � ' ) �

� ) & * ' ) �

* & � ' ( �

$ % & + ' ) �

� � � �

# � � .

OUTDOOR AIR PANEL SIZES

15 TON UNITS 21-1/2” X 43”

20 TON UNITS 32-1/2” X 43”

FIGURE 5 : UNIT CENTER OF GRAVITY

Page 25: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 25

FIGURE 6 : UNIT DIMENSIONS DHE/DHG180 & 240 (RAINHOOD)

� � � � � � � �

� � � � � � � � � � �

� � . � � � � / 0 � � �

� � � � � 0 � �

� � � � � 1 � � � � � � � � � 2 � � � 1 2 � 1 "

� � � � � � � 3 � �

� � � � � � 3 �

� � � � �

� � � � � 0 � �

� � � � � 1 � � � � � � � � � � � 2 � � � 1 2 � 1 "� � � � � � � 3 � � � ' � � � � � � � 3 � � � � � � �

� � � � � . � � � � / 0 � � � � � � � � � 0 � �

� � / �

� � � � � � � � � �

� � � � 4 � � 0 � �

� 5 � 6 � 1 � � � �

� � 1 � � � � � �

� � 2 � � � 1 2 � 1 "� � � � � � � � � � � �

� � � �

� � � � 1 � 7 � � 1 � � � � � � "

� � � � � # � � . � 0 � � # � � .

� � � � � � � �

� � � � � . � � 0 � � � � � � 0 � �

+ 8 �

8 8 & � ' ( �

, ( �+ 8 & � ' $ �

* �

+ $ & � ' $ �

� 8 & � ' ) �

( �

FIGURE 7 : TYPICAL UNIT APPLICATIONS

Page 26: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

26 Unitary Products Group

FIGURE 8 : UNIT 4 POINT LOAD

FIGURE 9 : UNIT 6 POINT LOAD

� � � � � �

9

9

� � � � � �

TABLE 3: DHE/DHG 4 POINT LOADS WEIGHT DISTRIBUTIONUNIT TOTAL A B C D

DHE180 2060 483 525 548 504

DHE240 2206 568 814 888 620

DHG180 2300 539 563 612 586

DHG240 2500 538 563 715 684

TABLE 4: DHE/DHG 6 POINT LOADS WEIGHT DISTRIBUTIONUNIT TOTAL A B C D E F

DHE180 2060 322 336 350 365 351 336

DHE240 2260 325 368 412 431 385 339

DHG180 2300 351 367 392 416 399 375

DHG240 2500 334 350 426 502 481 407

Page 27: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 27

1. The 2” space between the ducts allows for “jumping” anexisting roof joist.

2.The 58-1/2” overall dimension of the ducts allowsductwork penetration between roof joists that arespaced on 72” centers.

NOTE: Ducts can be installed into the curb from the roof. Allelectrical and gas line connections can be made inside thecurb.

FIGURE 10 : UNIT ROOF CURB DIMENSIONS

FIGURE 11 : ROOF CURB DUCT OPENINGSDIMENSION

FIGURE 12 : CUT AWAY OF ROOF CURB

Page 28: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

28 Unitary Products Group

FIGURE 13 : TYPICAL ROOFTOP INSTALLATION

Page 29: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 29

NOTES

Page 30: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

30 Unitary Products Group

Page 31: 036-21035-002-D-0602 YORK

036-21035-002-D-0602

Unitary Products Group 31

Page 32: 036-21035-002-D-0602 YORK

Subject to change without notice. Printed in U.S.A.Copyright © by Unitary Products 2002. All rights reserved. Supersedes: 035-21035-002-C-0500 036-21035-002-D-0602

Unitary 5005 NormanProducts York OKGroup Drive 73069