MECON LIMITED REGD. OFF: RANCHI 834002 STANDARD TECHNICAL SPECIFICATION OIL & GAS SBU, DELHI TITLE AIR CONDITIONING AND VENTILATION SYSTEM DOCUMENT NO. Page 1 of 16 MEC/TS/05/E9/035 REVISION : 0 EDITION : 1 DISTRIBUTION LIST OF CONTROLLED COPIES SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C 2. 02 MRR, Delhi 3. 03 ED (OIL & GAS)

Upload: vinay-nagvanshi

Post on 20-Dec-2015

12 views

Category:

Documents


0 download

DESCRIPTION

Technical Specification for HVAC system

TRANSCRIPT

Page 1: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 1 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Page 2: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 2 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

SPECIFICATION

FOR

AIR CONDITIONING AND

VENTILATION SYSTEM

Page 3: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 3 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

SPECIFICATION NO. - MEC/TS/05/E9/E/035, R-0

Page 4: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 4 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Page 5: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 5 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

(ELECTRICAL SECTION)MECON LIMITED

DELHI 110 092

Page 6: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 6 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Page 7: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 7 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

CONTENTS

Sl. No. Description

1.0 SCOPE

2.0 CODES AND STANDARDS

3.0 ENVIORMENTAL REQUIREMENTS

4.0 TECHNICAL DATA

Page 8: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 8 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

5.0 EQUIPMENT AND SYSTEM DESCRIPTION

6.0 TESTS

7.0 DOCUMENTATION

8.0 SHIPPING

9.0 SPARE PARTS AND SPECIAL TOOLS

10.0 DATA SHEET

Page 9: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 9 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Page 10: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 10 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Page 11: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 11 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

PREPARED BY: CHECKED BY: APPROVED BY: REVISION ISSUE DATE :

(Vinay Nagvanshi) (B.R.Satpathy) (D.G. Majumder) 0 Jun, 2013

AMENDMENT STATUS

Page 12: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 12 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Clause / Paragraph / Annexure / Exhibit / Drawing Amended

Page No.

Revision Date By

(Name)

Verified

(Name)

Page 13: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 13 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Clause / Paragraph / Annexure / Exhibit / Drawing Amended

Page No.

Revision Date By

(Name)

Verified

(Name)

Page 14: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 14 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Clause / Paragraph / Annexure / Exhibit / Drawing Amended

Page No.

Revision Date By

(Name)

Verified

(Name)

Page 15: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 15 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

1.0 SCOPE

This specification covers the Air conditioning and Ventilation design, Engineering, Manufacturing, painting, inspection & testing at manufacturer’s works and delivery to site inclusive of packing and transportation and commissioning at site as per this specification & data sheet and performance guarantee of Air Conditioning and Ventilation Systems. The equipment offered shall be complete in all respects. Any material or accessories, which may not have been specifically mentioned in the specifications but which are usually necessary for satisfactory, safe, trouble free, operation shall be provided without any extra charges.

2.0 CODES AND STANDARDS

Page 16: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 16 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

All equipment, systems and practices shall conform to those contained in the following publications, norms/guidelines, standards, acts and rules.

- Publications of Bureau of Indian standards (BIS)- American Conference of Governmental Industrial Hygienists (ACGIH) publication

USA.- Interplant standard specifications (IPSS) for steel plants.- Publications of International standards organization (ISO).- VDI stipulation of vibration level.- ARI Standard 550-92.

Page 17: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 17 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

- ASHRAE handbook- Handbook of Air Conditioning System Design by ‘Carrier Air Conditioning

Company’- Indian electricity rules

The list furnished above for standards and norms may not cover certain aspects or products. In such cases where norms/standards/guidelines other than those listed above are followed, the Contractor shall furnish a copy of such documents in support for the Purchaser’s perusal and acceptance of this project. Whenever a contradiction is found between the different documents, the decision of the Purchaser’s shall be final and binding.

Page 18: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 18 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

3.0 ENVIRONMENTAL CONDITIONS

The following ambient design data shall be considered for selecting and sizing various equipment for air conditioning and ventilation systems:

SEASON TEMERATURE HUMIDITYSUMMER 50 30RAINY 32 80WINTER 10 --

Page 19: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 19 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

4.0 TECHNICAL DATA

The air conditioning shall include central air conditioning / water cooled package type air conditioning systems for Control room, Server room and other rooms require air conditioning facility. Substation, Switch gear room, MCC room, VFD room, UPS room cable cellar / basement and other room require ventilation facility shall be provided with washed air supply system with pressurization of 2-3 mmWC positive pressure & maximum temperature of 270C. The system shall include air washer unit, centrifugal fan, dry panel filter, 100% stand by pump sets, ducting net work, supply air grills, gravity dampers etc. The equipment shall be installed in ventilation room of adequate size.

Page 20: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 20 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Exhaust ventilation shall be provided for battery rooms, pump house, transformer rooms, store, toilets and other areas emitting heat / fumes. The system shall include wall mounted axial flow fan with louver shutter / cowl with bird screen at the outlet side.

Mono rail beam with handling and hoisting facilities shall be provided for air conditioning and ventilation equipments in AC Plant room, AHU room & ventilation room.

The layout of premises for ACVS to be prepared by contractor shall be such that the ventilation room, AC plant room/AHU room shall be located suitably adjacent to the served premises.

Page 21: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 21 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

The Contractor shall clearly specify basis of design being offered along with heat load calculations, Ventilation (Ach) calculation and back up guarantee on his design.

Contractor shall furnish schedule & brief specification of air conditioning and ventilation systems with the offer.

A. Air conditioning systemThe different air conditioned rooms shall be maintained at 23+20C and 55+5% RH. The contractor shall provide split air conditioner/window air conditioner for personal comfort only to maintain maximum temperature of 250C(maximum) in shift in charge rooms, senior

Page 22: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 22 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

officers and other room if any.. The quantity shall be as per requirement and same shall be decided during detail engineering.

The contractor shall provide rain canopy at outdoor condensing unit of split air conditioner.

The capacity of air conditioning systems shall be decided based on equipment heat load in the premises, building heat load, illumination, occupancy heat load and other heat load. Minimum 10% safety margin shall be considered over and above calculated value.

` Type of air conditioning system to be provided as per the following guide lines

Page 23: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 23 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Type of Air Conditioning System Capacities of AC system

(i) Split air conditioner / Window air conditioner

Premises with cooling load less than 5 TR.

(ii) Water cooled package air conditioners

Premises with cooling load between 5 TR to 25 TR.

The package AC unit shall consist of reciprocating compressor, water cooled condenser, fan and other standard accessories. Cooling tower and 100% stand by condenser water pump sets shall be provided. The package AC unit capacity shall be 5TR / 7.5TR only. If system

Page 24: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 24 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

capacity is more than 10TR and upto 25TR, multiple number of AC units of similar capacity with minimum 50% stand by shall be provided. No other capacity will be accepted.

If air conditioning systems is provided with microprocessor control, manual over ride shall be provided for operation of the unit in case of failure / mal functioning of micro processor for central air conditioning unit/package air conditioning unit.

B. Ventilation systemTemperature inside substation, switch gear room, cable cellar / basement and other room with pressurized ventilation facility shall be maintained to 380C ( Maximum ) by the provision of suitable air washer unit of minimum 90 % saturation efficiency.

Page 25: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 25 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

The temperature inside the cable tunnel and areas being exhaust ventilated shall not exceed 3º C above ambient temperature at any part of the year.

Ventilation equipment (Centrifugal fan, Air washer, filter, pump sets etc. ) shall be installed in the Ventilation room. Monorail beam with chain pulley block shall be provided in the ventilation room having fan motor 18.5 Kw and above.

2-3 mm WC pressurization shall be maintained in the supply air ventilated premises. The capacity of the systems shall be decided on the basis of total heat dissipated in the premises. However minimum air changes/ hour shall be 15 in case of washed air supply system and 20

Page 26: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 26 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

air changes/ hour for fresh filtered air supply system & exhaust ventilation systems. 10% safety margin shall be considered over and above of calculated value.

C. Detail heat load calculations for ventilation and AC system shall be submitted first by the contractor before submitting any detail engineering drawing.

Fire damper interlocking provision with fire detection system shall be considered for all electrical premises, cable cellar / basement, cable tunnel susceptible to fire hazard premises shall be provided in air conditioning & ventilation room.

Page 27: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 27 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

The air distribution system shall be sized to have a constant frictional drop along its length. The maximum air velocity shall be restricted to 8 m/sec for air conditioning and 10 m/sec for ventilation ducts. All Grills/Diffuser shall be selected to give maximum room or space, coverage and low noise characteristics. The noise level within the air conditioned premises shall be restricted to 65 dB (A). Acoustic insulation shall be provided inside duct surface for a length of 5 m from package AC / AHU mouth. Fan installed in battery rooms shall be spark proof construction and motor flame proof construction and painted with acid resistant paint.Noise level of equipment shall not exceed 85 dB(A) at 1m distance from all equipment of ACVS unless stated otherwise elsewhere.IS: 655 shall be followed for construction of ducting however the sheet thickness for ducting shall not be less than 1mm GI.

Page 28: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 28 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Any other premises not specifically mentioned in the TS but required to be provided with air conditioning / ventilation shall be provided with suitable air conditioning / ventilation systems to maintain the required temperature and humidity.

The schedule of equipment list as envisaged for the facilities of AC & ventilation systems in different rooms is been listed in Annexure I.

5.0 EQUIPMENT AND SYSTEM DESCRIPTION

Brief description of main equipment is indicated below.

1. Air-conditioning system by water cooled package air conditioner:

Page 29: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 29 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

The Package Air Conditioner System will comprise of:

Package type air conditioning unit comprising of water cooled condenser, hermetic/semi hermetic sealed HCFC (R-22) refrigerant based reciprocating compressor, cooling refrigerant pipe line, blower, insulated cabinet, instruments and controls.

Thermal insulation over condensate drain line to avoid condensation over cold surface.

Condenser cooling water network comprising of natural draft cooling tower, circulating water pumps with 100% standby arrangement, pipe & pipefitting,

Page 30: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 30 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

pot strainer, valves, instruments and controls.

Ducting network with damper, acoustic and thermal insulation, supply air diffuser, return air grills etc.

Thermal insulation shall be provided in supply air ducting, return air ducting, chilled water piping, expansion tank etc. for all air conditioning systems as per GS. The thickness of insulating material shall be 50mm for ducting outside the served premises. Ducting outside the served premises for washed air supply shall also be thermally insulated with minimum 40mm thick insulation.

Page 31: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 31 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Humidity control arrangement with strip heater.

Make-up air filter with damper.

All electrical and Instrumentation accessories including MCC for air conditioning and ventilation system, temperature sensor, cables etc.

2. Air conditioning system by split air conditioner:

The Split Air Conditioner System will comprise of

Package type out door unit comprising of air cooled condenser, hermetic sealed HCFC (R-22) based refrigerant reciprocating compressor, refrigerant

Page 32: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 32 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

pipe line, condenser cooling fan instruments and controls. The outdoor condensing unit shall be provided with rain protection canopy.

Package type indoor unit comprising of fan, cooling coil, instruments and controls.

Interconnecting refrigerant pipeline and condensate drain line shall be done to suit site.

3. Air-Conditioning System By Window Air Conditioner:

Window type air conditioner will comprise of air cooled condenser, hermetically sealed HCFC (R-22) refrigerant reciprocating compressor, fan, refrigerant piping,

Page 33: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 33 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

filter, supply air grills, instruments and controls etc.

4. Ventilation by air washer system

The Air washer type ventilation system shall comprise of :

Centrifugal SISW fan with drive and accessories such as flexible connections, VIV damper at fan inlet, flexible connection at fan inlet & outlet, ducting, duct line dampers as required, supply air grills, channel base etc.

Motorized VIV damper shall be provided if the system capacity is more than 50,000 m3/hr.

Page 34: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 34 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Air washer with spray sets, brass nozzle, air distributor, water eliminator, tank, casing, marine light, hermetic door for achieving the saturation efficiency of not less than 90% for air washer

Intermediate chambers before & after spray chamber with inspection door, marine light etc.

Circulating water pump sets with 100% standby provision.

Circulating water pipeline, Make-up water pipe line, Drain pipe line of air washer with pipe & pipe fittings, valves, instruments etc.

Ducting network with damper, supply air grill/ diffuser.

Page 35: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 35 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Dry panel filters with fixing frame

Gravity damper.

All electrical and Instrumentation accessories including MCC for air conditioning and ventilation system, temperature sensor, cables etc.

The sheet thickness for air washer tank shall be 5 mm and for the body of the air washer shall be 3.15 mm MS sheet. The internal of air washer shall be galvanised / zinc spray coated.

Intermediate chambers shall be made of minimum 3.15 mm MS sheet. The internal shall be galvanised / zinc spray coated.

Page 36: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 36 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

The face velocity of air through air washer shall not be more than 2.5 m/sec.

Resistance to air flow in washing chamber shall not exceed 15 mmWC.

The face velocity of air through dry panel filter shall be limited to 2m/Sec.

5. Fresh air supply ventilation system to cable tunnel

The ventilation system shall comprise of :

Tube axial fan with drive and accessories and fixing frame

Dry panel filters with fixing frame

Page 37: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 37 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Ducting network and supply air grills if required.

Fire damper

6. Exhaust ventilation system

The exhaust ventilation system shall comprise of :

tube axial fan / propeller fan with drive and accessories

louver shutter / cowl with bird screen

fixing frame

Page 38: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 38 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

7. Cooling Tower

Type : Natural draft Frame Work : MS hot dip galvanized / FRP Casing/ Basin : RCC Louvers : FRP / Wooden Nozzles : Brass

Ladder : Galvanised steel ladder with safety cage & hand railing up to the top of tower. Inclined to 300 to the vertical

Cooling Tower Accessories :

Page 39: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 39 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

(i) Level switch at cooling tower basin (to be interlocked with pump)(ii) Make up connection with float valve (float made of copper), back up ball

valve(iii) Quick fill connection with ball valve(iv) Overflow connection(v) Drain connection with ball valve(vi) GI wire mesh 18 gauge strainer(vii) Equalising line of cooling towers with isolation valves

Cooling tower located at ground shall be provided with 1.5m wide cemented floor all

Page 40: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 40 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

around the cooling tower.

6.0 TESTS

6.1 Workshop Tests

All HVAC panel, motor and other accessories shall be tested completely and detailed in manufacturer’s workshop. All tests required by the codes and standards as well as all manufactures tests have to be performed. The test program for the work shop test has to be submitted prior to start of the tests in accordance with the Project Procedure Manual.

Page 41: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 41 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

a) Routine Test Visual Test HV test IR test Operational and Functional test BOM verification

Detailed test protocols of all tests performed have to be submitted prior to installation.

6.2 Site Tests

The site tests shall include the following steps:

Page 42: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 42 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Pre-installation check and testing, Pre-commissioning Commissioning and test on completion, Test runs, Performance guarantee test.

The aim of the tests is to ensure and prove the proper function of the complete scope.

7.0 DOCUMENTATION

Page 43: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 43 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Complete documentation shall be provided for the design, Engineering, calculation manufacturing, testing, commissioning, operation, maintenance and repair of the Air conditioning and ventilation system and its components. All documents shall be in English language.

The documentation HVAC shall include the following documents and drawings (minimum requirements):

a) General Layout and Arrangementb) Heat load calculation, ventilation calculation and Duct designingc) Technical data sheetsd) Calculations, protocols, certificates

Page 44: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 44 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

e) Spare parts listf) Operation and maintenance manualg) Reports of tests and commissioning with protocols.The documents listed above shall be handed over for approval. Special attention has to be given to the fact, that documentation must be submitted with sufficient time allocated for approval prior to manufacturing / assembly. Documentation has to be prepared in accordance with the relevant ISO standards or in the absence of relevant details in those standards the DIN standards shall apply.

The final documentation shall be delivered on paper in sufficient number and with exception of the signed protocols in electronic form, too. The type of the electronic files shall be agreed with the Client.

Page 45: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 45 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

8.0 SHIPPING

All equipment, material and spare parts shall be sufficient packaged and shall be shipped as a common delivery. The material, especially loose parts and spare parts shall be clearly labelled according to the designation.

9.0 SPARE PARTS AND SPECIAL TOOLS

The Contractor shall deliver all spare parts, which are necessary for commissioning and two years operation time (see “General Description of Project and Works”).Spare parts shall be available until ten years after commissioning.

Page 46: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 46 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

10.0 DATA SHEET

Data to be furnished by the Contractor during detail engineering.

a) Centrifugal Fan

Page 47: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 47 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

a Make & Model No.b Quantity no.c Type of bladed Capacity m3/he Static pressure and total pressure mm WCf Operating speed rpmg Critical speed rpmh Shaft power kW

Page 48: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 48 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

i Total Efficiency %j Motor rating, kW/ pole kW/ polek Acoustic lagging / silencer, as included l Material of constructionm Overall sizen Velocity at inlet & outlet of fan m/seco Static weight & dynamic weight of fan and

motorkg

Page 49: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 49 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

p Coupling details/V-belt detailsq Vibration levelr Material of construction & thickness of scroll,

blade, shroud, s back plate, shaft diameter mmt Noise level at 1m distance dB(A)u Bearing details

b) Fan Drive Motor Details

Page 50: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 50 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

a Type & makeb Voltage, phase & frequencyc Rated power kWd Speed rpme Starting/ pull out torquef Starter detailsg Line current

Page 51: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 51 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

h Starting currenti Overall efficiencyj Class of insulationk Type of enclosurel Any other information

c) VIV & Duct line Damper

Page 52: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 52 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

a Make, model and typeb Type of actuator, if applicablec Diameter of VIV mmd Motor kW/polee Material of construction and thickness

d) Dry Panel Air Filter

Page 53: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 53 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

a Make & Model. b Capacity. m3/hc Pressure drop. Mm WC

i ) When clean ii) When dirty

d Effective cross sectional free and face area m2 e Velocity through filter free and face area. m/secf Filtering panel material & construction details

Page 54: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 54 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

g Cleaning efficiency Vs particle size h Overall dimensions & no. of filters. i Fixing frame details. j Total weight. free and face area t & m2

e) Ducting

Page 55: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 55 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

a M2 of duct work m2b Weight of supports and flanges tc Material and thickness of duct work mm

f) Tube Axial fan / Propeller fanSl. No.

Characteristics Unit Value

a Make & Model

Page 56: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 56 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

b Capacity M3/hrc Quantityd Material of construction e Total pressure kgf/m2f Speed rpmg Size of fanh Drive details (kW & power supply)i Efficiency

Page 57: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 57 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

j Weight of fan & motor tk Details of non-return damper/louver shutterl Fixing frame

g) Air washing chamber with water tankSl. No.

Characteristics Unit Value

a Make & Model No.

Page 58: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 58 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

b Type of unit (Horizontal/vertical)c Overall dimensions mmd Weight with and without water kge Air flow capacity. m3/hf Air flow velocityg Total Pressure drop kgf/ m2h Material of construction, diameter and

numbers of spray header pipes & nozzles.

Page 59: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 59 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

i Make up water requirementj Details of make up, over flow, drainage,

supply and return water pipe linesk Amount of water and its pressure at the

nozzlel Material of construction and thickness of

casing, tank, air distributor platem Water tank capacity M3

Page 60: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 60 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

n Mounting supportso Details of mist /droplet eliminator: material

of construction, material thickness and depth.

h) Recirculating water system

Page 61: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 61 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

a Pump capacity & head, motor KWb Re-circulating piping & fitting;c Strainer & valve d Instruments– pressure gauge, temperature

gauge, water flow switch, manometer

Page 62: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 62 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

i) Package air conditioning system

Sl. No.

Characteristics Unit Value

a Make and modelb Quantityc Capacity TRd Overall dimension of Package AC Unite Air flow capacity of blower m3/hf Total Pressure mm WC

Page 63: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 63 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

i Fan Motor Kw kWj Fan RPM rpmk Compressor type, modell Compressor motor kWm Refrigerant typen Condenser type o Condenser material of constructionp Overall size of condenser

Page 64: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 64 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

q Material of construction and its thickness of casing

r Insulating material of casing s Total Power consumption.t Noise level at 1m distance dB(A)u Vibration isolation padv Refrigerant drier and strainer

Page 65: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 65 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

j) Insulation data sheetSl. No.

Characteristics Unit Value

a Make & Typeb Quantityc Density kg/m3d Thermal conductivitye Sound absorption co-efficientf Material of construction and its thicknessg Cladding material

Page 66: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 66 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

k) Cooling TowerSl. No.

Characteristics Unit Value

a Make & Model b Typec Quantityd Overall size of cooling towere Capacity of cooling. TRf Water flow m3/h

Page 67: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 67 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

g Air flowh Design water inlet temperature, outlet

temperaturei Material of construction and its thicknessj Speed. rpmk Drive details.l Shaft Power consumption.m Wheel diameter. mm

Page 68: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 68 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

n Efficiency.o Size of fanp Static & Dynamic weight of fan & motor

assembly t

q Bare weight and operating weight of cooling tower

t

r Noise level at 1m distance dB(A)s Fixing details.

Page 69: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 69 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

l) PumpsSl. No.

Characteristics Unit Value

a Make and model no. b Type of pump c Capacity m3/hr.d Total head m WCe Quantityf Material of Construction of

Page 70: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 70 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

Shaft ImpellerCasing

g Pump speed rpmh Shaft poweri Drive details

Motor makeMotor kW kW

Page 71: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 71 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

Class of insulation Frame size

j Bearing type & makek Type of couplingl Vibration levelm Noise level at 1 m distance dB(A)n Dutyo Weight of pump & motor separately t

Page 72: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 72 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

p Characteristic curves for pumps

m) Split Air Conditioner / Window air conditionerSl. No.

Characteristics Unit Value

a Make and model no. b Quantity

Page 73: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 73 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

c Capacity TRd Air flow m3/hr.e Flow direction and volume control grillf Material of Construction ofg Compressor type h Drive details and total power consumptioni Overall dimensionj Refrigerant type

Page 74: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 74 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

Sl. No.

Characteristics Unit Value

k Filter efficiencyl Weight of unitm Noise level at 1 m distance dB(A)n Accessories included

Page 75: 035 Ts Hvac Panel

MECON LIMITEDREGD. OFF: RANCHI 834002

STANDARD TECHNICAL SPECIFICATION

OIL & GAS SBU, DELHI

TITLE AIR CONDITIONING AND VENTILATION SYSTEM

DOCUMENT NO. Page 75 of 16

MEC/TS/05/E9/035 REVISION : 0

EDITION : 1

DISTRIBUTION LIST OF CONTROLLED COPIES

SL. COPY NO. DISTRIBUTION NO. 1. 01 ED I/C

2. 02 MRR, Delhi

3. 03 ED (OIL & GAS)

APPROVED BY: ISSUE DATE ISSUED BY

-x-x-x-