01_current for sag-dip testing - part 1
TRANSCRIPT
-
7/28/2019 01_Current for Sag-dip Testing - Part 1
1/4
____________________________________________________
Page 1 of 4
Voltage Dip Testing: How Much Current Must the Dip Generator Deliver ?
Part 1: Experimental Standard Test Load
Alex McEachern, Senior Member, IEEE
Power Standards Lab, Emeryville, California, USATEL ++1-510-658-9600 FAX ++1-510-658-9688
ABSTRACT
Current required by electronic loads during and aftervoltage dip testing is investigated. A standard test load is
constructed. This load requires only 45 amps nominal,
but actually requires 700 amps, or more, at the
conclusion of a voltage dip. If this peak current is notavailable, the load falsely appears to meet the testing
requirements. For this reason, test equipment for
performing voltage sag tests must be capable of providingvery high surge currents. Electronic sources, such asamplifiers, are generally not adequate. Transformer-
based sag generators with fixed taps (not variable
transformers) are generally capable of sufficient surgecurrent.
Keywords: sag, dip, immunity, testing, SEMI F47, IEC
61000-4-11, 61000-4-34, mains, power line
I. VOLTAGE SAG TESTING AND AVAILABLE CURRENT
Several standards, including SEMI F47 [1], IEC 61000-4-11 [2], and IEC 61000-4-34 [3], require testing electronic
equipment with voltage dips. Voltage dips are brief
reductions in AC voltage, typically lasting a second orless.
It is not widely understood that electronic loads, at the
conclusion of a voltage dip, may require far more currentthan their nominal current draw indeed, they may need
more current by a factor of 15 or more. In other words, a
load that is rated at 40 amps during normal operation may
actually require 600 amps or more for proper dip testing.
If the load is tested with a source that cannot provide this
increased peak current, failure modes such as blown fusesand open circuit breakers may be missed.
For this reason, electronic sources that provide limited
current such as amplifiers should be used for dip
testing with caution and skepticism about the results.
Transformer-based dip generators can generally deliver
sufficient current.
II. TEST LOAD FOR DEMONSTRATING DIP CURRENT
Fig. 1 Single-phase test load for determining voltage dip waveforms,typical of the power input circuit of single-phase electronic loads such
as adjustable speed drives. The bridge rectifiers BR1 are rated for
5 000 amps peak, and the capacitor C1 has an ESR of less than 8 m .
Fig. 2 Test load schematic shown in Fig 1. R1 is a 10-ohm, 10kW
air-radiant resistor. Hand-held meter (at left) shows scale. Nominal AC
current is 45 Amps RMS, but rises to 750 Amps peak after a voltage dip.
-
7/28/2019 01_Current for Sag-dip Testing - Part 1
2/4
____________________________________________________
Page 2 of 4
After many dip tests of real-world equipment, a test load
was constructed (Fig 1 and Fig 2). To simplify analysis,
the test load was limited to single-phase. To make the
results useful throughout the world, a test voltage of 240V
was selected.
The nominal AC current drawn by the test load is
approximately 45 amps RMS. To be conservative, a 150-amp fuse (not shown in photos) was selected. However,
as will be seen below, even this fuse melted several times
during the dip testing. Testing was performed with a
commercially-available sag/dip generator [4], modified todeliver up to 1750 amps peak. Typical results from a
voltage sag are shown below.
Cursor: -15.7ms 177.82 Volts www.PowerStandards.com
-500
-300
-100
100
300
500
Volts
L2-L3 load - m illiseconds - 12/22/03 8:15:40 AM
-40 4 48 92 136 180 224 268 312 356 400
Fig. 3A Typical voltage sag on AC mains 50% for 18 cycles.
Cursor: -15.7ms 317.54 Volts www.PowerStandards.com
-125
0
125
250
375
500
Volts
Ch 21 (1000V) - m illiseconds - 12/22/03 8:15:40 AM
-40 4 48 92 136 180 224 268 312 356 400
Fig 3B Voltage on capacitor C1 during sag
Cursor: -15.7ms . Am ps www.PowerStandards.com
-1000
-600
-200
200
600
1000
Amps
L2 Ld (1000A) - m illiseconds - 12/22/03 8:15:40 AM
-40 4 48 92 136 180 224 268 312 356 400
Fig 3C Current on AC mains reaches 700 amps peak
Cursor: 0m s 44.58 Am ps(rms) www.PowerStandards.com
-125
0
125
250
375
500
Amps(rms)
L2 Ld (1000A) (rm s) - m illiseconds - 12/22/03 8:15:40 AM
-40 4 48 92 136 180 224 268 312 356 400
Fig 3D Same as Fig 3C, but expressed as RMS current.
As expected, capacitor C1 partially discharged through
resistor R1 during the dip. At the conclusion of the dip,
capacitor C1 recharged rapidly. The current into the
capacitor was limited only by the source impedance of the
AC mains, the Equivalent Series Resistance (ESR) of thecapacitors, and the forward impedance of the rectifiers.
The key observations for Fig 3 are as follows:
Figure 3B shows that useful voltage remains oncapacitor C1, so the equipment may continue to
operate during the dip
Figure 3D shows that the pre-dip nominal
current is 45 amps RMS
Figure 3C shows the peak current after the dip is
700 amps.
A careful review of the waveforms indicates that the
source impedance of the AC mains is the most significant
limit on the current. The source impedance, in this case,had a magnitude of approximately 100 m, which
includes the impedance of the cabling and the dip
generator, in contrast to the ESR of the capacitors
(approximately 8 m) and the forward impedance of thebridge rectifiers (approximately 1 m each, or 2 m
total).
At the conclusion of the sag, the voltage on the capacitorC1 is approximately 175 volts, and the peak AC mains
voltage is approximately 241 volts. The difference of 66
volts, with a source impedance magnitude ofapproximately 100 m, readily explains the 700 amp
peak current.
Of course, if the AC mains source impedance had beenlower, the peak current would have been higher. Also, if
the capacitor had been more completely discharged, the
peak current would have been higher.
In other tests, not shown here, with the same load andlonger duration sags, at the end of the sag the peak current
reached 1650 amps. The load, of course, is rated for 45
amps RMS, so the contrast is somewhat startling.
III. FUSE OPERATION AT THE END OF A SAG
For test purposes, the test load of Fig 1 was equipped witha 150-amp fuse. This rating seemed more than adequate,
as the test load actually draws approximately 45 amps
nominal.
However, the fuse operated (opened) after a few voltage
sags. Fig 4 shows the waveforms.
-
7/28/2019 01_Current for Sag-dip Testing - Part 1
3/4
____________________________________________________
Page 3 of 4
Cursor: 20m s 178.8 Volts www.PowerStandards.com
-500
-300
-100
100
300
500
Volts
L2-L3 load - m illiseconds - 12/22/03 8:16:45 AM
-40 12 64 116 168 220 272 324 376 428 480
Fig 4A Voltage sag, with fuse opening at conclusion of sag.
Cursor: 0m s .49 Am ps www.PowerStandards.com
-1000
-600
-200
200
600
1000
Amps
L2 Ld (1000A) - m illiseconds - 12/22/03 8:16:45 AM
-40 12 64 116 168 220 272 324 376 428 480
Fig 4B The 800-amp current surge at the end of the dip was sufficient
to open the 150-amp fuse.
Cursor: 0m s 45.21 Am ps(rms) www.PowerStandards.com
-125
0
125
250
375
500
Amps(rms)
L2 Ld (1000A) (rm s) - m illiseconds - 12/22/03 8:16:45 AM
-40 12 64 116 168 220 272 324 376 428 480
Fig 4C Same as Fig 4B, but expressed as RMS amps. Note pre-dipcurrent is 45 amps RMS, a reasonable level for a 150-amp fuse.
Cursor: 0m s 318.52 Volts www.PowerStandards.com
-125
0
125
250
375
500
Volts
Ch 21 (1000V) - m illiseconds - 12/22/03 8:16:45 AM
-40 12 64 116 168 220 272 324 376 428 480
Fig 4D Voltage on capacitor C1. Note brief increase in voltage at endof dip, followed by continued decrease after fuse opens.
The key observations for Fig 4 are as follows:
Figure 4C shows that the pre-sag nominal
current is 45 amps RMS
Figure 4A shows that the 150-amp fuse operatedat the end of the sag.
This load, as designed, clearly cannot handle this voltagedip even with a 150-amp fuse, the fuse opens.
However, if this load had been incorrectly tested with a
dip generator capable of providing only a few hundred
amps peak which seems reasonable, but is in fact
wrong, for a load that requires only 45 amps nominal, the
load would not have blown its fuse. It would have been a
false passing result.
CONCLUSION
Voltage dip immunity testing is a useful, practical
engineering tool. It produces products that are strongerand more reliable. Like any engineering discipline,
experience leads to the discovery of pitfalls and incorrect
shortcuts.
One pitfall is testing using a dip generator that cannot
produce sufficient peak current. Sufficient is difficult to
define, but in the real-world examples shown in thispaper the peak current required was 15 times the rated
nominal current.
The commercially-available transformer-type dip/swellgenerator [4] used for the testing in this paper was capable
of delivering sufficient peak current.
Electronic sources are rarely rated for delivering
sufficient peak current for dip testing.
ACKNOWLEDGEMENTS
The author gratefully acknowledges the contribution of
Edward WINTERBERGER, who constructed the test loaddescribed in this paper. MIKE QUINN ELECTRONICS, of
Oakland, California, provided as always excellentsurplus parts at very low cost for the construction of the
test load. I am grateful for their help. Any errors, of
course, are solely my own responsibility.
-
7/28/2019 01_Current for Sag-dip Testing - Part 1
4/4
____________________________________________________
Page 4 of 4
REFERENCES
[1] SEMI F47-0200, Specification for Semiconductor
Processing Equipment, Voltage Sag Immunity.SEMI, Santa Clara, California, USA. 02-2000
[2] IEC 61000-4-11 Ed. 2.0, Testing and MeasuringTechniques voltage dips and short interruptions
immunity tests.
[3] IEC 61000-4-34 DRAFT, Testing and MeasuringTechniques voltage dips and short interruptions
immunity tests equipment greater than 16 amps.
IEC Document 77A/444/CD
[4] Power Standards Lab Industrial Power Corruptor
Model IPC-480V-200A,
http://www.PowerStandards.com/SagGen.htm
Alex McEachern (M 1984, SM 1996) isthe President of Power Standards Lab inEmeryville,California.
Over the last 20 years he has taught
graduate-level power quality coursesand/or has supervised the installation ofelectric equipment in the United States,Canada, Croatia, Japan, Hong Kong,
China, South Africa, Germany, France,Singapore, Switzerland, England, Scotland, Mexico, NewZealand, and Australia.