01 ats presentation

68
UTC Fire & Security EMEA Distribution ATS Product Presentation 15/02/2011

Upload: victor1

Post on 03-Nov-2014

216 views

Category:

Documents


20 download

TRANSCRIPT

Page 1: 01 ATS Presentation

UTC Fire & Security EMEA Distribution

ATS Product Presentation

15/02/2011

Page 2: 01 ATS Presentation

2 /UTC Fire & Security/

Agenda

•Introduce Participants/Trainer•ATS product range overview•Management software possibilities•Practice/exercise•Questions

Page 3: 01 ATS Presentation

3 /UTC Fire & Security/

A True Family concept

• Available in different sizes• Integration of intrusion and access control• All panels run on the same software• One user interface• All panels can work with all accessories• Upgrade from:

ATS1000>ATS2000>ATS3000>ATS4000

Page 4: 01 ATS Presentation

4 /UTC Fire & Security/

ATS Panels

ATS1000

ATS4000

ATS4500

ATS3000

ATS2000

Page 5: 01 ATS Presentation

5 /UTC Fire & Security/

Everything you need!

• Management Software adds CCTV & Fire

• Alarm reporting through all communications media

• Hardwired, wireless, addressable inputs

Page 6: 01 ATS Presentation

6 /UTC Fire & Security/

ATS Hardware - Overview

ATS1000 ATS2000 ATS3000 ATS4000

Power 1A 2A 2A 2A

Inputs on board 8 8 8 16

Max inputs 32 64 128 256

Std outputs on board (oc-relay) 4 4 4 4

Max outputs (relay/op) 128/ 256 128/256 128/ 256 128/ 256

Max battery in box 2x7.2Ah 18 Ah 18 Ah 2x7.2Ah// 18Ah

Page 7: 01 ATS Presentation

7 /UTC Fire & Security/

ATS Hardware - Overview

ATS1000 ATS2000 ATS3000 ATS4000

Memory extension 1/4/8Mb No Yes * Yes * Yes

Max readers (RAS; Remote Arming Station)) 16 ** 16 16 16

Max DGP (DGP= Data Gathering panel) 15 15 15 15

Wireless (ATS1234) Yes Yes Yes Yes

Access control (ATS1250) No Yes Yes Yes

Transmission PSTN/ISDN/GSM Yes Yes Yes Yes

Transmission TCP/IP (ATS1809) No Yes Yes Yes

Page 8: 01 ATS Presentation

8 /UTC Fire & Security/

ATS Memory - Overview

ATS1000 ATS2000 ATS3000 ATS4000

Alarm groups (Std/max) 128 128 / 138 128 / 138 128 / 138

Door groups (Std/max) 10 10 / 138 10 / 138 10 / 138

Time zones (Std) 24 24 24 24Holidays (Std/max) 24 24 / 64 24 / 64 24 / 64History – intrusion (Std/max) 200 200 / 1000 200 / 1000 200 / 1000History – Access (Std/max) 10 10 / 1000 10 / 1000 10 / 1000Macro logics 24 24 24 24Max users (standard ) 50 65000 65000 65000Max users (configuration soft IUM) 50 2000 2000 65000

Central stations 4 4 4 4

Page 9: 01 ATS Presentation

9 /UTC Fire & Security/

ATS Control panels General Features• On-board zones and local Zone expansion• Local output expansion• ATS control Panel data bus to connect Data

Gathering Panels (DGP’s)• Switched mode power supply

- Battery deep discharge protection- Dynamic battery testing

• External siren with driver option• On-board PSTN dialer• MI extesion bus

Page 10: 01 ATS Presentation

10 /UTC Fire & Security/

ATS Control Panels Customised solutions; standard components(Input) Events can be customised to have a conditional output

Pre-programmed zone types already offer 98% of the common required conditions

24 Macro logical equations will complete the remaining 2% of the special required conditions

INPUTOUTPUT

Kernel

Event Handler

Zone 1....................

Zone 256

Type 1....................

Type 71

EF 1 Output 1....................

Output 255

Output ConditionInput Condition

.....

.....

.....EF 255

ATS MASTER Decision Model

INPUT OUTPUT

Page 11: 01 ATS Presentation

11 /UTC Fire & Security/

Modular: Growing with customer needsAdd new components without replacing the initial equipment

IC3

ATS7100/ATS7110

Page 12: 01 ATS Presentation

12 /UTC Fire & Security/

ATS Layout

+12 , 0V, D+, D- = Databus

A, B = PSTN line inAx, Bx = Line out

Main power/ Battery

Inputs : 1t/m 8

Page 13: 01 ATS Presentation

13 /UTC Fire & Security/

ATS Connections

RS232 to Titan via ATS1630 serial cable

ATS1801/1802

Opt. Memory

TST1 Jumper

To ATS1202

Zone 9-16 active

To ISDN, GSM, voice or ISDN interface

LK18 = KILLBack to default setting

To ATS1810/1811/1820

Page 14: 01 ATS Presentation

14 /UTC Fire & Security/

Outputs onboard

External Siren EOL (1K) (12V of Driver)

Internal Siren

Panel outputs Panel Output nr.External Siren (12 V of Driver) ATS 1/2/3/4000 16Internal Siren (12 V) ATS 1/2/3/4000 15Strobe (12 V) ATS 2/3/4000 2Relais (C/NO/NC) ATS 3/4000 3SW + SW - (12 V) ATS 3/4000 251

Strobe (12V)

Page 15: 01 ATS Presentation

15 /UTC Fire & Security/

ATS Control Panel Data BusEvery ATS Control Panel includes a RS485

system databus to connect:

> A maximum of 15 Data Gathering Panels (DGP) to provide extra zones and outputs

> A maximum of 16 Arming Stations (RAS) which can be any combination of keypad or reader

> Remote devices can be up to 1.5 km from an ATS control panels. RS485 data busx 16 RAS x 15 DGP

Page 16: 01 ATS Presentation

16 /UTC Fire & Security/

ATS Control Panel Data Bus

A physical connection between 2 or moreTo communicate to;

ATS4001Panel

ATS1201DGP

ATS1100RAS

DisplayATS1100RAS

DisplayATS1201

GPIATS1201

DGP

Max. 1,5 km FTP or STP CAT5 kabel

Max. 16 RAS’s Max. 15 DGP’s

T T

T Terminator setBus001 Rev.01

Page 17: 01 ATS Presentation

17 /UTC Fire & Security/

ATS Control Panel Data Bus TopologyWhich network structures are allowed?

Point to Point 1 2

Daisy chain 1 322 3 ....

Backbone with stubs (max. 9 meter)

1 72 4 5

3 6

Page 18: 01 ATS Presentation

18 /UTC Fire & Security/

ATS1210/1211 DGP

8 C 7 6 C 5 4 C 3 2 C 1 Inputs

J4 to ATS 1810,1811,18

20

Power + DataDGP Address

Page 19: 01 ATS Presentation

19 /UTC Fire & Security/

ATS1201 DGP

DGP Address

options

ATS 1810/1811/18

20

Ext. Siren Output

8 Inputs Tamper Data bus +12v, 0v, D+, D-

Terminator

To 1202

Page 20: 01 ATS Presentation

20 /UTC Fire & Security/

ATS 1202 Input expansion

Zone n° to useSW1 SW2 SW3 SW4print n° 1 : 9-16 ON OFF OFF OFFModule n° 2 : 17-24 OFF ON OFF OFFModule n° 3 : 25-32 OFF OFF ON OFF

J2 J2

J2

J3 J3

J3Naar DI

Page 21: 01 ATS Presentation

21 /UTC Fire & Security/

DGP with ATS1202 expanders

PanelRAS DGP DGP DGP

• Expansion with 8 inputs per ATS1202• Max. 32 inputs per DGP

Page 22: 01 ATS Presentation

22 /UTC Fire & Security/

ATS components Bus accessories

>ATS1740 Isolators>ATS1744 Data bus isolators>ATS1742 Closed loop modules>ATS1741 RS485 - RS232 converters>ATS1743 RS485 - Fiber modules

Page 23: 01 ATS Presentation

23 /UTC Fire & Security/

ATS1744

4 way DATABUS ISOLATOR / REPEATER

Page 24: 01 ATS Presentation

24 /UTC Fire & Security/

ATS 1744 possibility

DATABUS

Panel

Page 25: 01 ATS Presentation

25 /UTC Fire & Security/

ATS 1744 possibility

DatabusPanel

AATS1744 BC D

E

Terminator set at A, B, D en ENo terminator set to C

Max length1500 m for AB en 1500 m for DE

Page 26: 01 ATS Presentation

26 /UTC Fire & Security/

ATS 1744 possibility

DatabusPanel

A

B

C ED2

ATS1744

ATS1744

Terminator set B, C, D and ENo terminator at A

Max length 1500 m for DE and for BC

Page 27: 01 ATS Presentation

27 /UTC Fire & Security/

ATS 1744 possibility

BUS DATAABCD

Panel

max. 1500m max. 1500m max. 1500m

Bus DataBCD

Bus DataBCD

Aux power+12V to AGND to B

Aux power+12V to AGND to B

A AB B

• Max. 4 x ATS1744 at one panel• Max length = 1500 m per databus• Use external power supply (dist. = > 100m)• Set terminators like normal databus

Page 28: 01 ATS Presentation

28 /UTC Fire & Security/

Advanced Wireless DGP ATS1234 -> 868 MHz, FM> Mother / Daughter board concept to meet local frequency and

security requirements> Range sensitivity & noise floor level indication> Range reduction test for commissioning> Up to 15 DGP’s connectable

Page 29: 01 ATS Presentation

29 /UTC Fire & Security/

Advanced Wireless DGP System Overview

> ATS4000 can connect up to 240 wireless devices> Up to 400 m range

1 2 8/15

max. 32 max. 32 max. 32

Page 30: 01 ATS Presentation

30 /UTC Fire & Security/

Intelligent Addressable System System Overview

ATS4000 can connect up to 240 addressable devices

max. 16max. 16

max. 32

Page 31: 01 ATS Presentation

31 /UTC Fire & Security/

Intelligent Addressable System Why Addressable Detectors?

Installer benefits> Cut down the installation time> Just 2/4 wires + address dip-switch> No detector configuration dip-switches> Less cable and connections, no EOL Resistors> Range, LED, walk-test… configured by TITAN> More options for diagnostic/service> Easier to extend a system> Commission report> Free topology possible

– No re-cabling required– Easy to install and extend

Page 32: 01 ATS Presentation

32 /UTC Fire & Security/

Cabling costs ATS addressable busReduced cabling lengthand number of connections (no “home-runs” from each detector)

Lower 2-wire cable cost (no expensive Cat 5)

Higher security (eachdevice has a unique ID)

Full free topology – Easy to add on devices

Enhanced remote diagnostics

Page 33: 01 ATS Presentation

33 /UTC Fire & Security/

ATS Product Overview

Integrated Access Control

Page 34: 01 ATS Presentation

34 /UTC Fire & Security/

ATS components Accessories Miscellaneous>Memory expansions (1, 4 or 8MB)>Extend the number of users>Supports all Wiegand readers up to 48 bits>Different card formats on one system>Learning mode

>Cards>Card Programmers>Colored covers (ATS1190)

Page 35: 01 ATS Presentation

35 /UTC Fire & Security/

Integrated Access Control

Flexible and Highly Secure Most systems work according to an ON/OFF modeThe ATS is much smarter> Copes with flexibility of working schedule> Deals with:

– Contractors & cleaning staff– Security staff– Facilities open 24hr/24hr– High security applications– Banking, vault & ATM applications

Page 36: 01 ATS Presentation

36 /UTC Fire & Security/

Integrated Access Control

>Standard door access functionality to 16 doors (connected to main panel)

>Readers and keypads on the BUS>Reader interface to adapt 3rd party reader >Time zone programming>Holiday programming>Flexible card / PIN configuration

Page 37: 01 ATS Presentation

37 /UTC Fire & Security/

Access ControlDoor Access definition

•Door access provides means for managing access through doors based on a valid credential (PIN, Badge or both), valid access rights within specified time periods

•Most common type of access required

Page 38: 01 ATS Presentation

38 /UTC Fire & Security/

ATS Keypads and Readers

>ATS111x Keypads with or without integrated card reader

>ATS115x Robust PIN / Card + PIN reader>ATS116x Mifare Card/Card + PIN reader>ATS119x Card / Card + PIN readers> Can be connected to the communication

bus

Page 39: 01 ATS Presentation

39 /UTC Fire & Security/

RelationIntrusion - Access

Keypads Users

Door/Floor groupsAlarm Groups

Areas Timezones Doors

Readers

Page 40: 01 ATS Presentation

40 /UTC Fire & Security/

ATS Product Overview

Communication

Page 41: 01 ATS Presentation

41 /UTC Fire & Security/

Communication

Directly from panel to comport PC (ATS1630)- limited time, max. 4 hours.> - access via service menu (menu 7>5)

> Computer interface (ATS1801/ATS1632)> - permanent connection

Page 42: 01 ATS Presentation

42 /UTC Fire & Security/

ATS Control Panels Communication

All ATS Control Panels are provided with an onboardPSTN dialer for:

> Central Station Reporting> Remote up- / downloading> Management Connections

RS232 programming port forConfiguration

Optional ATS1801 communication modulefor permanent management connection

Page 43: 01 ATS Presentation

43 /UTC Fire & Security/

Connection by using J18.(RS232)

• Press menu + 1278 + enter• Go to menu 7 + enter• Press code 1278 + enter• Press 5 + enter, for direct connection• Press “clear” > display showed “REMOTE”• Select “activate” In TITAN

This connection is made by using cable ATS1630

Page 44: 01 ATS Presentation

44 /UTC Fire & Security/

Connection by using the ATS 1801• Direct connection can be made by TITAN

• Direct connection is not time limited

This connection is made by using cable ATS1632

Page 45: 01 ATS Presentation

45 /UTC Fire & Security/

RS232

Requirements :>shielded>length: 15 m official

Advise :>Use datacable CAT5 shielded or better>length: about 30 m possible

(surroundings depends)

Page 46: 01 ATS Presentation

46 /UTC Fire & Security/

Solution

ATS4001Paneel

ATS1201DI

ATS1100GI

DisplayATS1100

GI

DisplayATS1201

DIATS1201

DI

Max. 1,5 km FTP of STP CAT5 kabel

Max. 16 GI's Max. 15 DI's

ATS1801

ATS1741

ATS1741

PM811

Titan systeem

T Terminator geplaatst

T

T

T T

Bus009 Rev.01

Max. 1,5 km FTP ofSTP CAT5 kabel

Max. 30 m FTP of STP CAT5 kabel

Page 47: 01 ATS Presentation

47 /UTC Fire & Security/

ATS Reporting All communication Paths available

Page 48: 01 ATS Presentation

48 /UTC Fire & Security/

ATS Reporting Alarm Reporting Centre

4 Central Stations / 2 phone numbers per CS

ATS Control Panel

Transmission link

CS 1

CS 2

CS 3

CS 4

Page 49: 01 ATS Presentation

49 /UTC Fire & Security/

ATS Control Panels MI extension busAll ATS Control Panels are provided with a MI

extensionbus to connect:

•ATS712x ISDN (EURO)

•ATS7300/7310 GSM

•ATS7200 Voice

Page 50: 01 ATS Presentation

IP Connection ATS1809

ATS1809 Universal Interface

Page 51: 01 ATS Presentation

51 /UTC Fire & Security/

ATS1809 Universal InterfaceOutcome•Know how to connect ATS1809•Know how to configure ATS1809

Page 52: 01 ATS Presentation

52 /UTC Fire & Security/

ATS1809 Universal InterfaceFeatures•μC Linux-based•Connects to ATS1801•Two purposes:

>management application connection (Alliance)>reporting to IP receiver (GE Network Receiver)

•Web-browser configurable•Strong encryption

Page 53: 01 ATS Presentation

53 /UTC Fire & Security/

ATS1809 Universal InterfaceRequirements• Use version 00.06.09 or later

> flash upgrade> Wire RTS/CTS signals

• Configure ATS Panel’s computer address (Installer menu 29) Address 0 not allowed

• Jumper DEF for default IP address (192.168.0.100)• Obtain from locale IT following IP network settings

> static IP address> network mask> gateway address

Page 54: 01 ATS Presentation

54 /UTC Fire & Security/

DEFNot used

RST

ATS1809 Universal InterfacePCB

DEF – Default IP addressRST – ResetRS232 panel comms

Page 55: 01 ATS Presentation

55 /UTC Fire & Security/

ATS1809 Universal InterfaceComputer settings•Select “Use the following IP address”

>IP: 192.168.0.X (last octet “X” not 100)>Subnet: 255.255.255.0>Gateway: if required

•Web browser: >Disable Auto detect settings or auto configuration

Page 56: 01 ATS Presentation

56 /UTC Fire & Security/

ATS1809 Universal InterfaceConfiguration•Open web-

browser and enter default IP address: 192.168.0.100

• Click “Login”

Page 57: 01 ATS Presentation

57 /UTC Fire & Security/

ATS1809 Universal Interface

•Login>Username & password:

– ADVISOR MASTER– 998765

•Static Address Parameters>Enter IP address>subnet mask >gateway address

Page 58: 01 ATS Presentation

58 /UTC Fire & Security/

ATS1809 Universal InterfaceCentral Station Parameters• Configure connection list

>First 3 Stations for GE Network Receiver>Consider use of Two fish Encryption

Alarm

Management

{{

Page 59: 01 ATS Presentation

59 /UTC Fire & Security/

ATS1809 Universal InterfacePanel configuration• Panel Physical Address

• Panel computer address (same as installer menu 19 >> 29)

•Panel Security Password •Always submit changes•Then select “Restart

Communications” to activate settings

Page 60: 01 ATS Presentation

60 /UTC Fire & Security/

ATS1809 Universal InterfaceFirewall• Consider use of

firewall • Set default rule to

deny all connections• Set rules to open all

ports for specific IP address

> Management application (UDP)

> ATS1806 Web browser (TCP, 80)

Page 61: 01 ATS Presentation

61 /UTC Fire & Security/

ATS1809 Universal InterfaceTroubleshoot• Check if red & green LED

both flash (indicate 1809 <> panel comms)

• Ping static address• Use web browser• Check through browser

> IP address, port, encryption> Encryption key> Panel/computer address> Security password

Page 62: 01 ATS Presentation

62 /UTC Fire & Security/

ATS1809 Universal InterfaceExercise•Make connection to Universal Interface via

web browser•Configure the UI using the guidelines

above>Configuration as defined in class

•Troubleshooting>Ping for standard troubleshooting>Ethereal/WireShark or equivalent for advanced

troubleshooting

Page 63: 01 ATS Presentation

63 /UTC Fire & Security/

TITAN Software

Windows Vista

Page 64: 01 ATS Presentation

64 /UTC Fire & Security/

ATS8100 TITAN Standard Configuration package + simple management

• ATS configuration package• Commisioning and maintenance tool• Easy database switching• Multiple systems, multiple panels in system• Single client, single user access• Connect directly (RS232), PSTN, GSM, ISDN

• All functionalities for daily user management

Page 65: 01 ATS Presentation

65 /UTC Fire & Security/

ATS8100 TITAN Standard TITAN Diagnostic™

There is no equivalent in the market !EN50131 maintenance requirements> Full remote diagnostic> Remote maintenance > Tool for on site commissioning

Page 66: 01 ATS Presentation

66 /UTC Fire & Security/

ATS8100 TITAN Standard Remote services

TITAN remote services • 100% of the ATS commands are accessible remotely

using TITAN:– Set / Unset areas individually– Unlock doors, inhibit detectors, – enable / disable users– …and much much more

Page 67: 01 ATS Presentation

67 /UTC Fire & Security/

.

Page 68: 01 ATS Presentation

68 /UTC Fire & Security/

Thank you !

Any questions?