-sump-water-pumps-5
DESCRIPTION
-Sump-Water-Pumps-5TRANSCRIPT
Absolute Project Solution Company Nigeria Limited
DOCUMENT NO: KPPP-AP-020-DAT-30005
Sump Water Pump - DataSheet
4/6/2012 R1 Issue for Review Abdul .G
Prepared By Checked By Approved ByIssued
Date Rev. No.
Revision Status
This document contains information that are proprietory to APROSOL Ltd, which must be held in confidence. Disclosure, Reproduction, or other use without the prior written consent of Aprosol
Process Data Sheet for Sump Water Pump1 Tag No. : PBA -2004A/B Client:
2 Service: Sump Water Pump Plant Location:
3 P & ID No. : Manufacturer: -
4 Calculation Ref. : Purchase Order No. : -
5 Pump Type: Centrifugal
6 Number of Units: 2
7 Connected In (Series/Parallel) Parallel
8 Operation (cont/int): Intermittent
9 Driver Type: Motor
10 Auto Start Required: Yes
11 Process Trip Signal: Yes
12 Fluid : Oily Water
13 Corrosion / Erosion due to sulfur content yes ( less than 0.05mg/kg)
14 Volumetric Flowrate: (Max) gpm 55
15 (Normal) gpm 50
16 FLUID PROPERTIES
17 Viscosity: Normal cP 1.12
18 @ min. temp.
19 Vapour Pressure: Normal psia 0.6
20 @ min. temp.
21 Specific Gravity Normal 1.025
22 @ min. temp.
23 SUCTION CONDITIONS
24 Source Pressure psia 21.7
25 Static Head ft 0.328
26 Line Losses - piping,strainer, filter, etc psi 7.9
27
28 Total suction pressure psia 13.93
29 Total suction head ft 31.4
30 DISCHARGE CONDITIONS
31 End of Line Pressure psia 43.5
32 Static Head ft 16.4
33 Total Line Losses psi 22
34
35 Total discharge pressure psia 86.3
36 Total discharge head ft 194.4
37 NPSH, DIFFERENTIAL PRESSURE AND POWER
38 Min NPSH available ft 11.8
39 Design differential pressure: psi 55
40 Design differential head: ft 163
41 Hydraulic power hp 1.6
42 Estimated efficiency: % 65
43 Estimated absorbed power: hp 3.25
44 Estimated shut in pressure: psia 60
45 DESIGN CONDITIONS
46 Pump casing pressure psig Note 1
47 Pump casing temperature (Max/Min) Note 1
48 Ambient temperature (Norm/Min) 85
49
50
R1 6-Apr-12 ISSUE FOR REVIEW (IFR)
Rev. Date Issue Description Originated Checked Approved Client
NOTE
1 Vendor to Confirm
Project No: SHEET
Datasheet No: 5 1 of 1