MHCO General Characteristics D.C. MEASURING CONVERTER Converter for D.C. Current and/or Voltage measurement. Direct connection to D.C. mains rating up to 4 kVcc. Fully isolated multi-voltage power suppy. Fiber optic connection between HV transducer and LV reciving unit. Measurement channel fully diagnosed The technical specifications reported are not binding and they should be agreed in the related contract. Transducers The transducer MHCO provide a measurement of current or voltage fully isolated and safe. The transducer includes three components: Transmitter, Riceiver, Fiber Optic. Transmitter The Transmitter, connected to the system, acquires the inputs and througth a fiber optic transmits it to the receiver. The test voltage isolation between inputs and power supply is equal to 20kV 50Hz 1min. Voltage Transmitter MHCO-TV Converter for Voltage measurement direct connection to D.C. line up to 4000V (voltage divider inside) Current Transmitter MHCO-TI Transmitter for measuring current, directly connected to the high voltage line through normal shunt . Current/Voltage Transmitter MHCO-TVI Transmitter current and voltage in a single unit directly connected to the high voltage line (max 4000Vcc) through the shunt. Riceiver Current and Voltage Receiver MHCO-RV MHCO-RI voltage measurements current measurements Fiber Optic The optical fiber used for the connection between the transmitter and receiver (equipped with ST connectors) must have the following characteristics: Plastic: 200u HCS - Glass: 62.5/125 The standard length of the optical fiber is 5 meters. (other lengths available on request). The Receiver connected via optical fiber to the transmitter has three configurable linear analog outputs, - one relay output for alarm and internal fault. MHCO-RI MHCO-RV MHCO-TVI M02 NG 18 -I -Rev.

Upload: dokhue

Post on 19-Feb-2019

230 views

Category:

Documents


0 download

TRANSCRIPT

MHCO

General Characteristics

D.C. MEASURING CONVERTER

• Converter for D.C. Current and/or Voltage measurement.

• Direct connection to D.C. mains rating up to 4 kVcc.

• Fully isolated multi-voltage power suppy.

• Fiber optic connection between HV transducer and LV

reciving unit.

• Measurement channel fully diagnosed

The technical specifications reported are not binding and they

should be agreed in the related contract.

Transducers

The transducer MHCO provide a measurement of current or voltage fully isolated and safe.

The transducer includes three components: Transmitter, Riceiver, Fiber Optic.

Transmitter

The Transmitter, connected to the system, acquires the inputs and througth a fiber optic transmits it to the receiver.

The test voltage isolation between inputs and power supply is equal to 20kV 50Hz 1min.

Voltage Transmitter

MHCO-TV Converter for Voltage measurement direct connection to D.C. line up to 4000V

(voltage divider inside)

Current Transmitter

MHCO-TI Transmitter for measuring current, directly connected to the high voltage line through normal shunt .

Current/Voltage Transmitter

MHCO-TVI Transmitter current and voltage in a single unit directly connected to the high voltage line

(max 4000Vcc) through the shunt.

Riceiver

Current and Voltage Receiver

MHCO-RV

MHCO-RI

voltage measurements

current measurements

Fiber Optic

The optical fiber used for the connection between the transmitter and receiver (equipped with ST connectors) must have the following

characteristics: Plastic: 200u HCS - Glass: 62.5/125

The standard length of the optical fiber is 5 meters. (other lengths available on request).

The Receiver connected via optical fiber to the transmitter has three configurable linear analog outputs, - one relay output for alarm and

internal fault.

MHCO-RI

MHCO-RV

MHCO-TVI

M0

2N

G1

8-I

-Re

v.

2

Wiring Diagram - Standard version with external auxiliary power supply

MHCO-TV

Vaux

MHCO-RV

MHCO-TI

MHCO-RI

Vaux

MHCO-TVI

Vaux

V

I

OUTPUT 3

OUTPUT 2

OUTPUT 1

VauxEST.RESET

(OPTION)

ALARM

(OPTION)

DIAG.

OUTPUT 3

OUTPUT 2

OUTPUT 1

VauxEST.RESET

(OPTION)

ALARM

(OPTION)

DIAG.

MHCOTransducers

M0

2N

G1

8-I

-Re

v.

3

MHCOTransducers

Power supply voltage ( ) N.D.1

( ) (230)Vac 20%5 �( ) (33 70)Vdc2 �

( ) (85 160)Vdc3 �

( ) (110)Vac 20%4 �

Rated input voltage ( ) 200Vdc; ( ) 750Vdc; ( ) 1000Vdc; ( ) 1500Vdc; ( ) 3000Vdc; ( ) 4000Vdc.1 2 3 4 5 6

Input Impedance 20 M�

Outputs Fiber Optic free running serial output (type = 200.230.500 ST-ST)

Fiber Optic standard length 5m (max. 250m)

Measurement dynamic range 0 2Vn�

Measurement accuracy 0.1% Vn (-20 to +70)°C

Sampling frequency 32.2 kHz

Response time 0.5 msec. ( )compensated

Enclosure Material: BMCRF9 protection degree IP55

Connessioni A vite (M6) per ingressi di misura / ST per F.O. / Morsetti 2.5mm per Vaux2Connection terminals Bolt type terminals (M6) for inputs; ST for the F.O. ;

Power supply consumption �5 VA

Characteristics Voltage Transmitter MHCO-TVDirectly connected to the H.V. line via voltage dividerinternal

Screw type 2.5 mm for Power Supply2

Power supply voltage ( ) N.D.1

( ) (230)Vac 20%5 �( ) (33 70)Vdc2 �

( ) (85 160)Vdc3 �

( ) (110)Vac 20%4 �

Rated input current ( ) 60 mVdc; ( ) 80 mVdc; ( ) 100 mVdc; ( ) others on request.1 2 3 4

Outputs Fiber Optic free running serial output (type = 200.230.500 ST-ST)

Fiber Optic standard length 5m (max. 250m)

Measurement dynamic range ( ) ( )1 20 2 In; 0 10 In (x DIA / U-MLEs) - (1% 4)� � for auxiliary output

Measurement accuracy 0.1% In (-20 to +70)°C

Sampling frequency 32.2 kHz

Response time 0.5 msec. ( )compensated

Enclosure Material: BMCRF9 protection degree IP55

Connessioni A vite (M6) per ingressi di misura / ST per F.O. / Morsetti 2.5mm per Vaux2Connection terminals Bolt type terminals (M6) for inputs; ST for the F.O. ;

Power supply consumption �5 VA

Characteristics Current Transmitter MHCO-TIDirectly connected to the H.V. line across a normal measuring shunt

Diagnostic of Shunt's interruption Signalization via Fiber Optic

Screw type 2.5 mm for Power Supply2

M0

2N

G1

8-I

-Re

v.

Power supply consumption

Characteristics Voltage Receiver (MHCO-RV)

Power supply voltage

� 8VA

( ) N.D.1

( ) (230)Vac 20%5 �( ) (33 70)Vdc2 �

( ) (85 160)Vdc3 �

( ) (110)Vac 20%4 �

Measuring input Fiber Optic transmitter MHCO-TV

Outputs (configurable on request) 3 current loop outputs; Max. output power 0 7VA – 13 5V. .

Output accuracy 0.1% full scale (-20 to +70)°C

Response time < 0.5 msec.

Sampling frequency 32.2 kHz

Mesurement display 2 Led "ON" and "DIAG"

Diagnostic alarm relay Contact C/O. (Relay normally energized)

Deenergized for Internal Fault (Transmitter, Receiver, F.O. interruption, Power Supply failure)

Relay pick-up time < 200 msec.

Enclosure ABS protection degree IP42

Insulation 2500 V for 1 min. power supply / outputac

2500 V for 1 min. relay / outputac

Connection Terminals Bolt type terminals (2.5 mmq) - ST for Fiber Optic

Output 1 (terminals 1-2)

Standard output setting range

( ) 0 20 (30)mA 0 Vn (1.5Vn)1-1 � � �

( ) 4 20 (28)mA 0 Vn (1.5Vn)1-2 � � ��

( ) 0 10 (15)mA 0 Vn (1.5Vn)1-3 � � �

Output 2 (terminals 3-4) ( ) 0 20 (30)mA 0 Vn (1.5Vn)2-1 � � �

( ) 4 20 (28)mA 0 Vn (1.5Vn)2-2 � � ��

( ) 0 10 (15)mA 0 Vn (1.5Vn)2-3 � � �

Output 3 (terminals 5-6) ( ) 0 20 (30)mA 0 Vn (1.5Vn)3-1 � � �

( ) 4 20 (28)mA 0 Vn (1.5Vn)3-2 � � ��

( ) 0 10 (15)mA 0 Vn (1.5Vn)3-3 � � �

USCITA

OUTPUT1

USCITA

OUTPUT2

USCITA

OUTPUT3

USCITA DIAGNOSTICA

CHIUSO=FUNZ.NORMALE

APERTO=GUASTO

DIAGNOSTIC OUTPUT

CLOSE=NORMAL OPERATION

OPEN=FAULT

Alim. Aux.

Power Supply

Fiber Optic

Fibra Ottica

1

2

3

4

5

6

27

30

17

16

28

DIAG.

6

MHCOTransducers

( ) Other on request1-4

( ) Other on request2-4

( ) Other on request3-4

M0

2N

G1

8-I

-Re

v.

7

MHCOTransducers

Power supply consumption

Characteristics Current Receiver (MHCO-RI)

Power supply voltage

� 8VA

( ) N.D.1

( ) (230)Vac 20%5 �( ) (33 70)Vdc2 �

( ) (85 160)Vdc3 �

( ) (110)Vac 20%4 �

Measuring input Fiber Optic transmitter MHCO-TI

Outputs (configurable on request) 3 current loop outputs; Max. output power 0 7VA – 13 5V. .

Output accuracy 0.1% full scale (-20 to +70)°C

Response time < 0.5 msec.

Sampling frequency 32.2 kHz

Mesurement display 2 Led "ON" and "DIAG"

Diagnostic alarm relay Contact C/O. (Relay normally energized)

Deenergized for Internal Fault (Transmitter, Receiver, F.O. interruption, Power Supply failure)

Relay pick-up time < 200 msec.

Enclosure ABS protection degree IP42

Insulation 2500 V for 1 min. power supply / outputac

2500 V for 1 min. relay / outputac

Connection Terminals Bolt type terminals (2.5 mmq) - ST for Fiber Optic

Output 1 (terminals 1-2)

Standard output setting range

( ) 0 20 (40)mA 0 In (2 In)1-1 � � �

( ) 4 20 (36)mA 0 In (2 In)1-2 � � ��

( ) 0 10 (20)mA 0 In (2 In)1-3 � � �

( ) 0 15 (30)mA 0 In (2 In)1-4 � � �

Output 2 (terminals 3-4) ( ) 0 20 (40)mA 0 In (2 In)2-1 � � �

( ) 4 20 (36)mA 0 In (2 In)2-2 � � ��

( ) 0 15 (30)mA 0 In (2 In)2-4 � � �

( ) 0 10 (20)mA 0 In (2 In)2-3 � � �

Output 3 (terminals 5-6) ( ) 0 20 (40)mA 0 In (2 In)3-1 � � �

( ) 4 20 (36)mA 0 In (2 In)3-2 � � ��

( ) 0 10 (20)mA 0 In (2 In)3-3 � � �

( ) 0 15 (30)mA 0 In (2 In)3-4 � � �

Output 4 (terminals 7-8) Optional ( ) 4 20 mA -0.75In 1.5In4-1 � � ���

( ) 4 20 mA 0 1.25In4-2 � � ���

( ) 4 20 mA 0 1In4-3 � � ���

( ) 4 20 mA 0 1.33In4-4 � � ���

( ) 4 20 mA -0.75In 0.75In4-5 � � ���

( ) 4 20 mA -1In 1In4-6 � � ���

( ) 4 20 mA -2In 2In4-7 � � ���

( ) 4 20 mA -1.33In 1.5In4-8 � � ���

USCITA

OUTPUT1

USCITA

OUTPUT2

USCITA

OUTPUT3

USCITA DIAGNOSTICA

CHIUSO=FUNZ.NORMALE

APERTO=GUASTO

DIAGNOSTIC OUTPUT

CLOSE=NORMAL OPERATION

OPEN=FAULT

Alim. Aux.

Power Supply

Fiber Optic

Fibra Ottica

1

2

3

4

5

6

27

30

17

16

28

DIAG.

7

8 USCITA

OUTPUT4

OPZIONALE

OPTIONAL

M0

2N

G1

8-I

-Re

v.

8

MHCOTransducersOverall Dimensions - Transmitter (mm)

Overall Dimensions - Receiver (mm)

159

31

353570

52,5

120

Ø7

225

29

11

42,5

140

10

175

220

M6

10 200

60

75

95

10

MHCO-TVI

30

6970

42,5

140

52,5

120

Ø7

225

175

220

11

29

M6

20010

10

60

75

95

51

MHCO-T...

ON

DIAG

(*)90

62

45

160

3073

MHCO-R

1 52 3 4 6

30 2529 28 27 24 17 16

7

8

STANDARD

VERSION

(*) OUTPUT 4 - OPTIONAL

M0

2N

G1

8-I

-Re

v.

9

MHCOTransducers

R Seference tandard - EN50123 - IEC60255CE Directive

Dielectric test voltage IEC60255-5 cat IV - 2kV

EN50123

IEC60255-5

EN50123

(EN50124-1 cat OV4 - 18.5kV)

cat IV - 5kV

(EN50124-1 cat OV4 - 40kV)

Impulse test voltage

Enviromental Rif.Std. (IEC 60068)

Operation ambient temperature EN60870-2-2 class C1 (3k5) -10°C / +55°C

Environmental

testing( )Cold

( )Dry heat

( )Change of temperature

( )Damp heat, steady state

IEC60068-2-1

IEC60068-2-2

IEC60068-2-14

IEC60068-2-3

-10°C ; 16h

+55°C ; U.R.<=35%; 16h

+55°C ; -10°C ; 3h

+40°C ; U.R.<=93%; 96h

Resistance to vibration

Resistance to vibration and shock (bump-shock)

Sismatic stress resistance

IEC60255-21-1

IEC60255-21-2

IEC60255-21-3

class 2

class 1

class 2

10-500 Hz ; 2 g

10 g - 15 g

1 g (xy), 2 g (z)

CE EMC Compatibilità

Electromagnetic emission EN55011

class B

30-1000MHz (tab1 EN50081-2) A

0.15-30 MHz (tab1 EN50081-2) A10VConducted disturbances immunity test EN55022

level 3 80-1000MHz 80%AM B10V/mRadiated electromagnetic field immunity test EN60870-2-1 A.5.1

IEC61000-4-3

EN50082-2

EN50140, EN50204

EN50082-2

ENV50140

level 3

level 3

900MHz/200Hz A10V/m

Electrostatic discharge test EN60870-2-1 A.3.1

IEC61000-4-2

level 3 6kV contatto / 8kV aria B

Power frequency magnetic test EN60870-2-1 A.4.1

IEC61000-4-8

level 5 continui 100 A/m A50/60Hz

Conducted disturbances immunity test EN50082-2

IEC61000-4-6

level 3 (80 5)% AM1 kHz sinwave� A

Damped oscillatory magnetic field EN60870-2-1 A.4.3

IEC61000-4-10

level 3 30 A/m, 0.1 1 MHz�

Electrical fast transient/burst (Fast Trasient) EN60870-2-1 A.2.3

IEC61000-4-4

level 3 2kV (m.c.) B

Dumped Oscillatory waves EN60870-2-1 A.2.5

IEC61000-4-1

level 3 1kV (m.c.)

Power supply tollerance IEC60870-2-1 class DC3

class AC2

EN60870-2-1 VR3 �5%Residual power supply

Surge immunity test EN60870-2-1 A.2.2

IEC61000-4-5

level 3 8/20 s 2kV (m.c.) B

Voltage interruptions EN60870-2-1 A.1.5

IEC61000-4-11

20ms

Voltage ripple EN60870-2-1 A.1.4

IEC61000-4-11

A=B

Characteristics

Accuracy at reference value of influencing factors Class 0.2

Average power supply consumption RX 7 VA

Average power supply consumption TX 5 VA

Output relays

A.C. resistive switching = 1500VA (400V max)

rating 6 A; n = 250 VV

make = 30 A (peak) 0,5 sec.; break = 0.2 A, 110 Vcc,

L/R = 40 ms (100.000 op.) – Meccanichal life 10 op6

M0

2N

G1

8-I

-Re

v.

Transmitter Voltage - Order Code MHCO-TV - 3-6:

Type_MHCO-TV Power Supply3

0 = N.D.

1 = N.D.

2 = (33 70)Vdc�

3 = (85 160)Vdc�

4 = 110Vac 20%�

5 = 230Vac 20%�

Rated Input Voltage6

1 = 200 Vdc

2 = 750 Vdc

3 = 1000 Vdc

4 = 1500 Vdc

5 = 3000 Vdc

6 = 4000 Vdc

Empty = Power Supply

Transmitter Current - Order Code MHCO-TI - 2-1-1-2:

Type_MHCO-TI Power Supply2

0 = N.D.

1 = N.D.

2 = (33 70)Vdc�

3 = (85 160)Vdc�

4 = 110Vac 20%�

5 = 230Vac 20%�

Rated Input Current1

1 = 60 mVdc

2 = 80 mVdc

3 = 100 mVdc

Empty = Power Supply

Dynamic range1

1 = (0 2) In���

2 = (0 10) In���

Selfpowered version

SHUNT connection

2

1 = Positive

2 = Negative

Receiver Voltage - Order Code MHCO-RV - (12)-(22)-(32)-3:

Type_MHCO-RV Output 1( _ )1

1-1 = (0 20) mA���

1-2 = (4 20) mA�

1-3 = (0 10) mA���

O = with Options

(MHCO-RV-O-....)

Power Supply3

1 = N.D.

2 = (33 70)Vdc�

3 = (85 160)Vdc�

4 = 110Vac 20%�

5 = 230Vac 20%�

Output 2( _ )2

2-1 = (0 20) mA���

2-2 = (4 20) mA�

2-3 = (0 10) mA���

Output 3( _ )3

3-1 = (0 20) mA���

3-2 = (4 20) mA�

3-3 = (0 10) mA���

Receiver Current - Order Code MHCO-RI - (12)-(22)-(32)-(42)-3:

MHCO-RI Output 1( _ )1

1-1 = (0 20) mA���

1-2 = (4 20) mA�

1-3 = (0 10) mA���

Power Supply3

1 = N.D.

2 = (33 70)Vdc�

3 = (85 160)Vdc�

4 = 110Vac 20%�

5 = 230Vac 20%�

Output 2( _ )2

2-1 = (0 20) mA���

2-2 = (4 20) mA�

2-3 = (0 10) mA���

Output 3( _ )3

3-1 = (0 20) mA���

3-2 = (4 20) mA�

3-3 = (0 10) mA���

1-4 = (0 15) mA��� 2-4 = (0 15) mA��� 3-4 = (0 15) mA���

Output 4( _ )4

4-0 = None

4-1 = (-0.75 1.5) (In)���

4-2 = (0 1.25) (In)���

4-3 = (0 1) (In)���

4-4 = (0 1.33) (In)���

4-5 = (-0.75 0.75) (In)���

4-6 = (-1 1) (In)���

4-7 = (-2 2) (In)���

4-8 = (-1.33 1.5) (In)���

12

MHCOTransducers

Type_

O = with Options

(MHCO-RV-O-....)

(x DIA / U-MLEs)

4 = Specify

Fiber Optic - Order Code MHCO-FO - 1:

Fibra Ottica

1 = 5 mt (standard)

2 = ________mt (specifiy length)

ST - Connector

55 mm

Receiver Current (x DIA / U-MLEs) - Order Code MHCO-RI - (12)-(22)-(32)-(42)-3:

MHCO-RI Output 1( _ )1

1-1 = (0 20) mA���

1-2 = Not Available

1-3 = Not Available

Power Supply3

1 = N.D.

2 = (33 70)Vdc�

3 = (85 160)Vdc�

4 = 110Vac 20%�

5 = 230Vac 20%�

Output 2( _ )2

2-1 = (0 20) mA*���

2-2 = Not Available

2-3 = Not Available

Output 3( _ )3

3-1 = (0 20) mA���

3-2 = (4 20) mA�

3-3 = (0 10) mA���

1-4 = Not Available 2-4 = Not Available 3-4 = (0 15) mA���

Output 4( _ )4

4-0 = None

4-1 = (-0.75 1.5) (In)���

4-2 = (0 1.25) (In)���

4-3 = (0 1) (In)���

4-4 = (0 1.33) (In)���

4-5 = (-0.75 0.75) (In)���

4-6 = (-1 1) (In)���

4-7 = (-2 2) (In)���

4-8 = (-1.33 1.5) (In)���

Type_

O = with Options

(MHCO-RV-O-....)

*(10In)

Microelettrica Scientifica S.p.A. - 200 (MI) - Via Italy Tel. +39 02 575731 - Fax +39 02 57510940 - E-Mail: [email protected] Buccinasco Lucania, 2 -

www.microelettrica.com

This publication may be subject to alteration without prior notice. Therefore, a printed copy of this document may not be the latest revision. Please

contact your local representative for the latest update. The trademarks MS Microelettrica Scientifica, Knorr and Knorr-Bremse as well as the figurative

mark “K” are registered. Copyright © Knorr-Bremse AG and Microelettrica Scientifica SpA - all rights reserved, including industrial property rights

application. Knorr-Bremse AG and Microelettrica Scientifica SpA retain any power of disposal, such as for copying and transferring. per la copia e il

trasferimento.