KUWAITI STANDARD KWS 1893/2018 1 لصناعة لعامة ل الهيئة اPUBLIC AUTHORITY FOR INDUSTRY (PAI) KWS 1893:2018 لدنياود اقة والحدلطاءة اات بطاقات كفا متطلبت الهواءلطاقة لمكيفاك اءة استه لكفالسعات ذات ا حتى70,000 و.ح.ب./ساعةENERGY EFFICIENCY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR DX AIR-CONDITIONERS UP TO 70,000 Btu/h

Upload: others

Post on 20-Mar-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

1

الهيئة العامة للصناعة

PUBLIC AUTHORITY FOR INDUSTRY (PAI)

KWS 1893:2018

متطلبات بطاقات كفاءة الطاقة والحدود الدنيا

ذات السعاتلكفاءة استهالك الطاقة لمكيفات الهواء

و.ح.ب./ساعة 70,000حتى

ENERGY EFFICIENCY LABELLING

AND MINIMUM ENERGY PERFORMANCE

REQUIREMENTS

FOR DX AIR-CONDITIONERS UP TO 70,000 Btu/h

Page 2: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

2

Table of Contents 1. SCOPE .......................................................................................................................................... 4

2. OBJECTIVE ................................................................................................................................... 4

3. NORMATIVE REFERENCES ........................................................................................................... 4

4. TERMS AND DEFINITIONS............................................................................................................ 5

5. REGISTRATION REQUIREMENTS .................................................................................................. 7

6. MEPS ........................................................................................................................................... 8

7. NAME PLATE AND INSTRUCTION SHEET OR MANUAL ................................................................ 9

8. ENERGY RATING CLASSIFICATION ............................................................................................. 10

9. ENERGY LABELLING REQUIREMENTS ........................................................................................ 11

Page 3: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

3

تقديم

قامت الهيئة العامة للصناعة ضمن برنامج عمل اللجنة الفرعية لكفاءة طاقة المكيفات والمنبثقة من اللجنة الوطنية لقطاع

" موطلبفات بطاقفات اففاءة 1893 2018المواصففات الكهرباييفة واكلكورونيفة باعفاام المواصففة الفنيفة الكوقويفة قف

سوهالك الطاقة لمكيفات الهواء".الطاقة والحاوم الانيا لكفاءة ا

قوليففو 10 والصففام بوففا ق 15 \ 2018 وقففا اعومففات اففوا المواصفففة االيحففة ينيففة للراميففة يفف القففرا الففو ا قفف

2018.

Forward

The Public Authority for Industry (PAI), through the program of energy efficiency of air

conditioners subcommittee of (The National Committee for the Sector of Electrical and

Electronics Standards) prepared the Kuwaiti Technical Standard Number 1893:2018

“Energy Efficiency Labelling Requirements and the Minimum Energy Performance

Standard (MEPS) requirements for DX air conditioners”

Page 4: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

4

1. SCOPE

This standard specifies the requirements of 1) energy efficiency labelling and 2) Minimum

Energy Performance Standard (MEPS) for air-cooled DX air conditioners with capacities

including and up to 70,000 Btu/h. It is applied to units designed to operate in AC single

phase circuits of 240 V, and three phase circuits of 415 V with a frequency of 50 Hz.

2. OBJECTIVE

The objective of this Standard is to:

a) Provide detailed information on the performance and energy labelling

requirements which an air conditioning appliance has to meet in order to

carry a valid energy efficiency label;

b) Provide detailed information on the performance requirements which an air

conditioning appliance has to achieve in order to meet minimum energy

performance standard requirements.

3. NORMATIVE REFERENCES

The following normative references are applied, taking in account the differences in this

standard:

MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”.

GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing and

Rating for Performance".

GSO ISO 13253 “Ducted Air-Conditioners and Air-to-Air Heat Pumps – Testing

and Rating for Performance”.

Page 5: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

5

4. TERMS AND DEFINITIONS

For the purposes of this standard, the terms and definitions given in GSO/KWS

Standards mentioned in Section 3 and those below are considered.

Ducted air conditioners

An air-conditioner model configuration where the indoor side is situated remote

to the space to the conditioned. The conditioned air is supplied or extracted via

a duct.

DX air-conditioners

Air-conditioners that direclty cools the space by boiling the refrigerant in the evaporator, and condenser is cooled by ambient air (e.g.: mini-split unit, ducted split units, VRF, packaged units, etc.).

Non-ducted air-conditioner

An air-conditioner model configuration where the indoor side is situated partly

or wholly within the space to be conditioned. The conditioned air is supplied

and extracted directly to and from the conditioned space.

Package system

A self-contained air-conditioner with all its components assembeled into one

casing. It is usually installed outside of the conditioned space.

Rated capacity

The nominal rated capacity claimed by the manufacturer of an air-conditioner model determined as follows:

- Rated total cooling capacity As claimed by the manufacturer for

temperature condition T1 and T4. (Units: Btu/h).

The rated capacity at T4 appears on the energy label as ‘Capacity Output’

(Units: Btu/h).

Rated power

Effective power input of the air-conditioner model as claimed by the

manufacturer during the determination of rated cooling capacity.

(Units: W or kW.)

Split system

An air-conditioner with separate indoor and outdoor components that are

connected with refrigerant piping. The indoor unit usually lies within the conditioned space and may be installed or portable/mobile.

Star rating

The number of stars displayed on the energy effecincy label. Available stars are

Page 6: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

6

between a minimum of one and a maximum of four for window A/C type

and seven stars for other A/C types. It is considered as an indication of

the claimed energy efficiency of a model at rated conditions. A higher star

rating indicates a higher energy efficiency. It is derived from the tested EER .

T4

Test conditions where the outdoor design temperature is (48ºC DBT &26.9ºC WDT) & the indoor design temprature is (26.6ºC DBT & 19.4ºC WBT)

Page 7: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

7

5. REGISTRATION REQUIREMENTS

5.1 Information regarding registration requirement for energy labelling and

MEPS are available in Standarization & Metrology Department in Public Authority for

Industry (PAI).

5.2 For the energy efficiency labelling registration of an air-conditioner, the following shall be

submitted for the registration body:

a) Application form inaccordance with Appendix A

b) Test report in accordance with the most recent editions of GSO ISO 5151 or GSO ISO

13253, as applicable taking in account the differences mentioned in this standard.

5.3 Energy Label Validity (Acceptable Tolerance)

The energy label shall be accepted as valid when a single sample of an

appliance or unit model, tested for an initial screening test, meets the following

criteria for cooling, as applicable:

a) Tested effective power input (kW)..……………......…….≤ 1.05 x rated power.

b) Tested cooling capacity(Btu/hr)……………………..0.95 x rated capacity. c) Tested EER ……………………………….………….……..0.95 x rated EER. d) Tested power rating (kW/RT)…………………….……. ≤1.05 x rated kW/RT. e) Tested voltage (V) ................. 240V for single phase /415V for three phase 6% f) Tested frequency (Hz) …………………………………………………. 50 Hz. g) Testing conditions (T1,T4)................... (refer to Appendix B for T4 requirments).

Page 8: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

8

6. MEPS

The minimum energy performance standard MEPS value for the air conditioner in the

scope of this standard shall be greater than or equal to the value of Energy Effeicency Ratio

(EER), When calculating the cooling capacity and EER for both rated and tested

values at testconditions (T1) and test condition (T4) as follows:

Table 1: MEPS values for different types of the air conditioners at T1 & T4 test conditions

Air conditioner type

Rated Cooling Capacity (CC) (Btu/h) at test condition (T4)

EER Value ((Btu/h)/W)

Power rating per Refrigeration Tonnage PRT (kW/RT)

T1 T4 T1 T4

Window type

CC < 24,000 9.7 6.98 1.24 1.65

24,000 ≤ CC 8.5 6.12 1.41 1.95

Other types CC ≤ 70,000 11.5 8 1.04 1.5

Note: The MEPS requirements will be revised every 3 to 5 years to ensure alignment with

international standards.

Page 9: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

9

7. NAME PLATE AND INSTRUCTION SHEET OR MANUAL

In addition to any information needed to be displayed on the air-conditioner

unit, the following information shall be marked on the name plate of the air-

conditioner, in Arabic or English or both. The marking shall not be on a

detachable part of the unit and shall be indelible, durable and easily legible.

Any information related energy performance added shown in any part of the air-

conditioner unit or packaging shall not have any ambiguity or lead to miss

understand of the performance of the unit.

7.1 The information on the nameplate in Arabic or English or both shall include at least:

– Manufacturer’s name and/or trademark.

– Country of origin.

– Manufacturer’s model or type reference.

– Serial number of the unit.

– Rated voltage or rated voltage range (Volts).

– Rated frequency (Hz).

– For each of cooling test conditions T1 and T4 according to the standard

stated in Section 3, as applicable:

Rated current in Amperes.

Rated power input in watts or kilowatts.

Nominal cooling capacity in Btu/h (and any units of kW or

Kcal/h) when tested according to conditions stated in Section 3.

Rated Energy Efficiency Ratio (EER) in (Btu/hr)/W.

– Refrigerant used and mass of refrigerant charge in kg.

7.2 An instruction sheet or manual in both Arabic and English shall be delivered with each air-conditioner, including the following information:

– The information specified in Section 7.1.

– Dimensions of the unit in (mm) and its method of mounting.

– Minimum clearances between the various parts of the unit and the

surrounding framework in (cm or mm).

– Instructions necessary for the correct operation of the unit and any

special precautions to be observed to ensure its safe use and maintenance.

– Instructions for packing and unpacking the unit.

– Total weight of the unit including the refregerant charge.

– Any other additional information.

Page 10: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

10

8. ENERGY RATING CLASSIFICATION

8.1 The star rating is used for the energy efficiency labeling of products specified within the

scope of this standard (as defined in Section 1).

8.2 The energy efficiency class is then determined in accordance with the

following tables, where the EER (Energy Efficiency Ratio) is determined in

accordance with the test procedures of the normative refernceses mentioned in

Section 3 at condition T4.

Table 2: Star rating for window type air conditioners

Star Rating Power Rating Per Refrigeration Ton (kW/RT)*

EER limits (Btu/h)/W

1.80 ≥ PRT > 1.70 6.67 ≤ EER < 7.05

1.70 ≥ PRT > 1.60 7.05 ≤ EER < 7.50

1.60 ≥ PRT > 1.50 7.50 ≤ EER < 8.00

1.50 ≥ PRT 8.00 ≤ EER

* Testing at T4

Table 3: Star rating for all types of air conditioners except window type

Star Rating Power Rating Per Refrigeration Ton (kW/RT)*

Energy Efficiency Ratio (EER) (Btu/h)/W

1.50 ≥ PRT 1.45 8.00 ≤ EER < 8.28

1.45 ≥ PRT > 1.40 8.28 ≤ EER < 8.57

1.40 ≥ PRT > 1.35 8.57 ≤ EER < 8.89

1.35 ≥ PRT > 1.30 8.89 ≤ EER < 9.23

1.30 ≥ PRT > 1.25 9.23 ≤ EER < 9.60

1.25 ≥ PRT > 1.20 9.60 ≤ EER < 10.00

PRT ≤ 1.20 EER ≥ 10.00

*Testing at T4

Page 11: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

11

9. ENERGY LABELLING REQUIREMENTS

8.1 Information and Values Contained/Enclosed/included in the Energy Efficiency Label

All Arabic text shall be in font “Simplified Arabic”, size ### No Italic, bold, or

underlined text shall be used.

“ The font should be written “Simplified Arabic” for Arabic and “Times New

Roman” for English as illustrated in the Figures 1 to 3 . Fields (a) through (e) illustrated in Figure 2 shall comply with the following requirements:

(a) Field a This band shall terminate according to the appliance’s star

Rating.

(b) Field b This field shall include the regestration number and regestration

certificate issuance date.

(c) Field c This field shall include the tested value of energy efficienty ratio

(EER) for the appliance at T4 condition

(d) Field d This field shall include the power rating per refrigeration Ton (kW/RT)

at T4 condition.

(e) Field e The brand name shall be inserted here. The wording should be

complete and concise.They should have normal spacing of letter, line and word in the area allowed.

(f) Field f The model number shall be inserted here. The wording

should be complete and concise. In the case of split system, where the indoor and outdoor components have different model

numbers, model numbers for both shall appear on the label.

(g) Field g This field shall include the total power for the air-conditioner at T4

condition.

(h) Field h This field shall include the applicable refregerant type used for this

air-conditioner.

(i) Field i This field shall include the contry of origion

(j) Field j This field shall include the total rated cooling capacity (output

capacity) based on the rated input power at T4 condition.

(k) Field k This field shall include the compressor type.

Page 12: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

12

8.2 Sample Labels

Example of printed energy label for air-conditioning appliances are shown in

Figures 1 to 3.

8.3 Label Dimensions

Figure 3 shows the dimensions of label.

8.4 Placement of Energy Labels

The label shall be clearly located for visual site and adhered, on the right

front of the unit . for ease of custom procedures, an additional label may be

attached to the exterior of the packaging.

The label shall be existed on the unit when the unit is removed from its

packaging for display purposes, and split units shall have a label on both parts.

8.5 Material and Shape of Energy Labels

The label shall be of self-adhesive material, cut to the outline of the label.

A trim or die cut margin of up to 5 mm around the label is acceptable.

Page 13: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

13

Figure (1)

Example of an energy efficiency label for all air-conditioners (CC≤70,000 Btu/h)

Page 14: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

14

Figure (2)

Information of an energy efficiency label for all air-conditioners (CC≤70,000 Btu/h)

Page 15: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

15

Figure (3)

Dimensions of an energy efficiency label for all air-conditioners (CC≤70,000 Btu/h)

Page 16: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

16

Supplier or Vendor in Kuwait :

APPENDIX A

APPLICATION FOR REGISTRATION OF

AIR-CONDITIONERS FOR ENERGY LABELLING AND MEPS

(please type or print)

This Appendix sets out the required format for submitting an application for registration.

Application for registration of an air-conditioner for energy efficiency. I hereby apply for registration of an electrical appliance/s for the purpose of energy labelling.

In the Country of ................... (specify the country in which this application is made)

PART 1 APPLICANT INFORMATION

Applicant Name : ………………………………..................................................................... Company Name : ………………………................................................................................. Company Address : ………….......................................................................... ……………… P.O.Box: ………………………….... Post Code: ....................................................... Contact Person : (Name and Adrees and workplace in each sales country) Jop Title : …………………………………… Phone : …………………… Fax : …………………. Email : ..........................

No. Supplier or

Vendor Name

Contact Address

(Email Address, Phone, Fax)

License Number or Commercial Licenses

1

2

...

Page 17: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

17

Part 2 DESCRIPTION OF THE APPLIANCE

Model Name (if available)

Model Number or Family Number:

Model Number: (on indoor unit for split systems)

Model Number on Outdoor Unit: (split systems only)

Other Model Numbers to be included under this

registration:

Country of Manufacture:

Model Number(s) to appear on the Energy Label:

Date of manufacture traceability (of package unit or indoor unit if split system): Is the date of manufacture permanently marked on the rating plate in a non-encrypted format?

If yes, provide an example of the date format.

If no, provide details on how to determine (from the

serial number or other permanent markings for this model)

Yes Date format:

No Provide details:

'Date of manufacture traceability (of outdoor unit if split system):

Is the date of manufacture permanently marked on the

rating plate in a non-encrypted format?

If yes, provide an example of the date format.

If no, provide details on how to be determined (from the serial number or other permanent markings for this model)

Yes Date format:

No Provide details:

Does this model or family replace or supplement another

model or family with identical energy consumption and energy efficiency rating? (indicate correct answer)

Yes No

If yes, indicate relevant details:

Model Name

Model number

Registration number

Informtion about the components used in the

manfucturing: There must be complemantry documents for the

1- Compressor

Country of origin:…………………………….. Name of Manufacturer or his trading mark: ……

Page 18: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

18

materials used in the Manufacturing including

drawings figures, technical specifications

and product model accreditation (if any) for each

Compressor model number: ……………………

Compressor type: …………………….…………

2- Fan

Country of origin:………..

Name of Manufacturer or his trading mark: …….

Fan Model number: ………..

Fan type: …………………….

3- Heat Exchanger

Volume and description of the heat exchanger:….

.

Country of origin:………..

Name of Manufacturer or his trading mark: ……

. Fan Model number: ………..

Fan type: …………………….

3- Heat Exchanger

Volume and description of the heat exchanger:….

of the components mentioned here.

Part 3 TESTING AND TEST REPORT

Test Laboratory Type: (put () inside the appropriate box)

□ Own 'in-house' laboratory:

□ Independent laboratory:

Test Laboratory Name:

Test Laboratory Address:

Test Laboratory Location:

Test Laboratory Accreditation:

Test Standard Used:

Does this air-conditioner have separate indoor

and outdoor units

□ Yes □ No

Serial number of test unit/s and date tested: SERIAL NUMBER Unitary unit or indoor unit if split system

SERIAL NUMBER Outdoor unit if split system

Test date

Rated voltage and frequency of tested unit Package unit Unitary unit or indoor unit if split system

Outdoor unit if split system

Rated voltage or Rated voltage range (V)

Rated frequency (Hz)

Page 19: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

19

Tested voltage and frequency of tested unit Unitary unit or indoor unit if split system

Outdoor unit if split system

Tested voltage (V)

Test frequency (Hz)

Part 4 SPECIFIC APPLIANCE DETAILS Air-conditioner dimensions (Advisory only): (for split systems note only dimensions of the internal unit)

Width (mm): Height (mm): Depth (mm):

Power supply: □ Single-phase □ Three-phase

Rated Voltage (V): Rated Frequencu (Hz): Refrigerant Number : Please specify:

A/C Configuration 1—Air Distribution □ Ducted □ Non ducted

A/C Configuration 2—Type please specify:

Does this air-conditioner use a variable speed drive (inverter) or a multi-speed compressor?

□ Yes □ No

Page 20: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

20

* to 2 decimal places

** to 3 decimal place

DECLARATION

I declare that the details stated above are correct.

Signature of Applicant: ............................................. Date: ...................................

Office use only

Date received: ............................. Registration number:……………………….

Part 5 TEST RESULTS

TEST RESULTS—COOLING—CONDITION T4

COOLING POWER Rated Effective Power

Input (kW)*

Tested Cooling Power

Input (kW)**

COOLING CAPACITY Rated Total Cooling

Capacity (Btu/h)*

Tested Total Cooling

Capacity (Btu/h)**

EER (Btu/h)/W Rated EER **

Tested EER **

Page 21: ةعانصلل ةماعلا ةئي ìلا · MEW/R-6 “Energy Conservation Program, Code of Practice - Kuwait”. GSO ISO 5151 "Non-Ducted Air-Conditioners and Heat Pumps – Testing

KUWAITI STANDARD KWS 1893/2018

21

APPENDIX B

Test Conditions

1. For T4 conditions, the air conditioning units (other than window type) shall have a

power rating 1.5 kW/RT (EER8.0) while operating at maximum indoor air flow

and evaporative on-coil DBT 26.6 C (80 F) & WBT 19.4 C (67 F) and outdoor

(ambient) temperature of 48 C (118.4 F) & 26.9C (80.4F)

2. Units shall operate continuously at an outside ambient temperature of 52 C (125.6

F) for at least 2 hours without tripping.

3. Power supply (50 Hz):

Three Phase: 415 V 6 % (accepted range 390-440 V).

Single Phase: 240 V 6 % (accepted range 225-254 V).

4. Motor input 5 hp (3.73 kW) shall be three phase.