Course Objectives Familiarization of system Locations of:
HydrantsFDCKnox BoxFACPSprinkler Riser RoomLiquid Oxygen
Unique Fire Protection Element Smoke Curtain Kitchen Hood System Standpipe Pre Action & VESDA Systems
Hospital GroundsNORTHAmbulance Entrance
Main Entrance
Sprinkler Riser Room
Fire Dept. Connection
Knox Box
Enunciator Panel
Standpipe
Roof Acess
Fire Department ConnectionLocated on Jensen St. Side Of Hospital
You will need the knox key to
remove the caps on the FDC
Fire Alarm Control Panels
FACP located on floor one
in boiler room.
Annunciator panels
located on all floors.
Printer located near FACP prints
all activity associated with
fire systems
Sprinkler Riser Room
Water In
Pump Bypass Always Open
Fire Pump
Jockey Pump
Test Header Always Closed
Back To Riser
Double Check Valve
Floor 1 Riser/Standpip
e
Floor 2,3 & Roof
Riser/Standpipe
Standpipe
Isolation Valve Will Turn off
water to floors 2 & 3
Isolation Valve Isolates
2nd floor Sprinklers
Flow Switch Floor 2
2 ½ Inch Connection
Roof Top
Roof Access South
Stairwell
RoofStandpip
e
PIV
PIV
Dry Beyond Valve
Ceiling of south Stairwell
Roof Standpipe
Fire Curtain Separation
Located outside every elevator door. Curtains are activated with fire
alarm or sprinkler water flow
Located near stairway/ atrium on floor one.
Activated with fire alarm or water flow. In place to
prevent smoke migration between
floors.
Pre-Action System & VESDA System
Pre Action Located In
ClosetFloor 2VESDA Located On Floor 1 in
MRI Area
Loss Of Air Pressure Plus Activation Of
Smoke Detector Required For
Water To Enter The Sprinkler
Piping
Air Compressor
SolenoidHolds Water
BackVESDA Similar To Pre Action. Goes Into Pre Alarm Notifying Staff
Well In Advance Of Actual Fire.