© 2010 eaton corporation. all rights reserved. neutral switching of grounded sources dave loucks,...
TRANSCRIPT
© 2010 Eaton Corporation. All rights reserved.
Neutral Switching of Grounded Sources
Dave Loucks, PE
2 2
Switching Methods
• 3-Pole
• 3-Pole with Overlapping Neutral
• 4-Pole
3 3
Issues
1. Ground Discrimination
2. Transient Voltages
4 4
Ground Discrimination
• Identify source(s) feeding ground fault and clear
• Two scenarios:• Single Ground: Non-Separately Derived
• Multiple Ground: Separately Derived
5 5
Single Ground: Non-Separately Derived
• Issue• Ungrounded sources cannot be detected as
sources of ground current using CT at source.
Source 1 Source 2
CT 1output = IF
IF
IF IF IF
CT 2output = 0
IF
6 6
A Solution: Non-Separately Derived
Source 1 Source 2
IF
IF IF IF
IF
S1A
S2A
GFRelay
S1T
Reliable Tripping Power
S2T
7 7
Separately Derived System: 3-Pole
Source 1 Source 2
CT 1output = IF - 1/2IF = 1/2IF
IF
1/2 IF 1/2 IF
IF
1/2 IF 1/2 IF 1/2 IF
CT 2output = 1/2IF
• Issue• Multiple grounded sources with unswitched neutral
share ground current between each source
8 8
A Solution: Separately Derived
Source 1 Source 2
CT 1output = IF
IF
CT 2output = 0
IF
• Solution• Switch neutral to break “cheat” path for ground
current.
9 9
Separately Derived – Overlapping Neutral
• During the transition, this design looks the same as a 3-Pole device
• If a GF were to occur during this transition, same problems as with 3-Pole switching
Source 1 Source 2
CT 1output = IF - 1/2IF = 1/2IF
IF
1/2 IF 1/2 IF
IF
1/2 IF 1/2 IF 1/2 IF
CT 2output = 1/2IF
10 10
Transients
• So maybe an overlapping neutral has some problems with GF discrimination, but doesn’t 4-pole switching the neutral create transient overvoltages on the neutral?• After all, whenever current through an inductive circuit is
interrupted, you have the potential for transient overvoltage.
• We can calculated the magnitude of voltage of this transient from:
dt
diLVL
VL Transient Overvoltage developed across inductance
L Inductance (Henries)
di Differential (change) current (amperes)
dt Differential time (seconds)
VL i+ -
11 11
Can We Model Transients Accurately?
• To prove our model was accurate, we would need to compare our calculated transients on a switched neutral with measured transients from an actual lab experiment
• If our modeled values are equal to or greater than the values measured in the lab, then we could have confidence in our model• After all, if our model estimates higher transients
than what we measure in the lab, we can call our model “conservative” since actual transients will not be higher than our model.
12 12
Lab Test versus SPICE Model
Lab Test:
• 600 VL-L
• 10 kA rms available
• 60 Hz
• 49.1% PF
Equiv. SPICE Model
• 848.428 VL-L peak
• Z = 0.06 • 60 Hz
• X/R = 1.77• R = 0.0295137
• XL= 0.0522393
@ 60 HzL = 0.1385 mH
• For test, both systems are ungrounded
13 13
Problem: We Still Have an Unknown
• While we know L, di (change of current) …
• … we don’t know dt (time to change current)• How fast does a switched neutral operate?
• The faster it operates, the smaller the value of dt
• The smaller the value of dt, the higher VL
dt
diLVL
14 14
Progression of Arcing Contact
Time = 0 Time 1.1 ms Time 1.2 ms Time 5.5 ms
Total Arc Extinguishing Time 8.2 ms
Measured:
15 15
LT-SPICE Model
Note: “ungrounded” means capacitively grounded
16 16
Actual Lab Test
~ 530 V
Note: 530V / 848V = 63%
17 17
Model Matches Very Closely
• In fact, our model is “conservative” since model predicts higher transient than lab test
• Raises confidence that transients will be less
Current zero, arc
extinguishes
~ 530 V
Fault current
Arcing voltage
System voltage
~ 801 V
Note: 801V / 848V = 94%
18 18
Increase Size of Model
• Now that we have our switching model, we can change our source and see how the transients change
• New Test:• Source 1 – Utility
• 1500 kVA transformer, Z = 5.75%, 480Y/277 Vrms, 60 Hz, X/R = 6.6 (IFL = 1804 Arms, ISC = 31377 Arms
• Source 2 – Utility• Ratings same as Source 1
• Load• 600 Arms, 80% PF (X/R = 0.75)
19 19
Schematic Model
• Refer to Figure 21, page 20 and pages 14 - 19 for calculation of these values
20 20
GF and Transient Tests
• Non-separately derived (NSD) sources• Test 1: Open transition 3-pole switching (Figure 21)
• Separately derived (SD) sources• Test 2: Open transition 3-pole switching
• Test 3: Open transition 4-pole switching
• Test 4: Open transition phase 3-pole, closed transition neutral (overlapping) switching
21 21
Test 1: NSD 3-pole switching (page 20)
• NSD means only one source grounded• Assume GF system connected as shown in Figure
5 (page 4), so no GF discrimination problem
• 3-Pole switching means no neutral switching no neutral transient
Source 1 Source 2
IF
IF
IF
IF
IF
S1A
S2A
GFRelay
S1T
Reliable Tripping Power
S2T
22 22
Test 2: SD 3-pole switching (Page 21-22)
• SD means multiple grounded sources• Unswitched neutral means cheat path allows GF
currents to flow even through sources with 3-pole switching device open
Source 1 Source 2
IFIF
0.001847 24.01 H
0.001847 24.01 H
0.5 0.5
0.001847 24.01 H
0.001847 24.01 H
23 23
Test 2: SD 3-pole switching (Page 21-22)
24 24
Test 2: SD 3-pole switching (Page 21-22)
Actual GF current magnitude (1472
A peak)( 1041 A rms)
GF current measured at source 1 zero-sequence
CT (671.8 A peak)(475 A rms)
• Measured GF current is only fraction of actual
• … but that isn’t the only problem …
25 25
Test 2: SD 3-pole switching (Page 21-22)
• GF current is detected as flowing through de-energized source!
A, B and C phase current = 0
Neutral current = 733 A peak (533 A rms)
26 26
Switch Neutral
• These problems are well known and are the reasons why we switch the neutral of separately derived sources
• Two main methods:• 4-Pole
• 3-Pole with Overlapping Neutral Switching
• 3-Pole with Customer GF wiring
Method Advantages Disadvantages
4-Pole Switching No circulating current, so no possibility of desensitizing energized source GF relay and no possibility of nuisance tripping a GF relay protecting a de-energized source
Higher cost Larger footprint (size) Reported neutral transients*
3-Pole Switching with Overlapping Neutral
May be less expensive than true 4-pole since overlapping neutral typically is not rated for fault duty switching
During the time when both neutrals are connected, the same disadvantages as a 3-pole switch (nuisance tripping of GF relay on de-energized source and de-sensitizing energized source GF relay) exists
Added complexity and reduced reliability from an external switch controlled by levers and interlocks connecting to main switch
Added complexity to add GF relay switching as shown in Figure 5 to prevent nuisance tripping of de-energized source.
3-Pole Switching with Special GF Sensing Scheme
Less expensive than 4-pole or 3-pole with overlapping neutral
More complex wiring as de-energized sources have their trip circuits de-energized and their CT circuits paralleled with the CTs of active sources [11]
28 28
Transients
• What about the reported transients?
• What does the our model say?
dt
diLVL
• Equation of transient says it will be proportional to the current flowing in the neutral at the time of the interruption
• How much current flows in the neutral?
29 29
Neutral Current
• Balanced Load
• Unbalanced Load
30 30
Test 3: SD 4-Pole Balanced Load
31 31
Test 3: SD 4-Pole Balanced Load
• Very low or no current flows in neutral
• Modeled transient less than a 0.1 volt
0.1 V peak
0.1 V peak
Voltage across Source 2 neutral
Voltage across Source 1 neutral
32 32
Test 3: SD 4-Pole Unbalanced Load• Worst case is full phase current
• Modeled transient less than phase voltage
• Peak phase voltage: 277 Vrms*1.414 = 391 Vpeak
< 300 V peak Voltage across Source 2 neutral
< 300 V peak Voltage across Source 1 neutral
33 33
Unbalanced Load
• Need to confirm that GF current correctly isolates ground currents to only active sources• Notice that regardless of which source is switched,
only the active source detects GF current
Source 2 detected GF current
Source 1 detected GF current
Total GF current flowing
100 ms open transition
34 34
4-Pole “Non-Issues”
1. Worst case unbalanced load switching means neutral must switch load current• But it is a fully rated pole
2. Worst case, it must switch peak phase voltage• But it is a fully rated pole
3. Absolute worst case is that it might need to interrupt fault current• But it is already a fully rated, fault duty interrupting
pole
35 35
Test 4: SD 3-pole OL neutral (Page 25-26)
36 36
Test 4: SD 3-pole OL neutral (Page 25-26)
• Any transient from the switching only occurs if there is current flowing through the de-energized source.• That can occur during a GF
• Also, the problem is that a 3-pole OL switch is essentially a 3-pole switch during the switching time, so it suffers from the same problems of GF discrimination
37 37
Test 4: SD 3-pole OL neutral (Page 25-26)• Here a GF occurs during transition, but fault current is
divided between sources• Reduces current to relay that supposed to see it
• Nuisance tripping of relay that isn’t supposed to see it
Actual GF current increases higher than with 4-pole switching!
~ 1/2 peak GF current at source feeding fault (Source 2)
Balance of GF current flowing through overlapping neutral
38 38
Summary
• 4-Pole accurately measures GF currents
• 3-Pole with OL neutral does not accurately measure GF currents
• 4-Pole does not generate voltages that exceed normal phase voltage
• 3-Pole with OL neutral could create a transient during a GF
• 4-Pole does not increase magnitude of GF
• 3-Pole with OL neutral can increase magnitude of GF
39 39
References
• See page 28 of paper
• LT Spice is available free of charge from http://www.linear.com/ltspice
• SPICE models used in this paper as well as this PowerPoint can be downloaded from http://pps2.com/files/xfer/spice