| 1 universal lighting technologies ult marketing ballast basics i presented by: your name here
TRANSCRIPT
| 1Universal Lighting Technologies
ULT Marketing
Ballast Basics IPresented by: Your Name HERE
| 2Universal Lighting Technologies
Topic Outline
• Fluorescent Lamp & Ballast Functions
• Ballast Types
• Ballast Starting Methods
• Attributes and Measurements
• Advanced Ballast Definitions
• Standards & Regulations
• Lighting Retrofits & Energy Savings
• Controllable Lighting
| 2
| 3Universal Lighting Technologies
Before Fluorescent…
Incandescent lamps were the only available electric lighting source, and they are still common today for a variety of applications.
But… Incandescent lamps are not efficient and don’t last long.
Have you ever touched an incandescent or halogen lamp while it was on?
The heat that incandescent lamps generate demonstrate their inefficiencies as lighting sources.
Fluorescent Ballast Basics
| 3
| 4Universal Lighting Technologies
• Incandescent 18 LPW 750 hrs. life• Fluorescent 60-105 LPW 20,000+ hrs. life
Fluorescent lamps are significantly more efficient than incandescent lamps, using less energy and lasting significantly longer. This efficiency can be measured in terms of Lumens per Watt (LPW). This is similar to Miles per Gallon with an automobile.
Fluorescent lamps provide Energy Efficiency & Longer Life
For a basic understanding of fluorescent ballasts, a brief overview of fluorescent lamps is necessary:
Why Use Fluorescent?
| 4
| 5Universal Lighting Technologies
What makes a fluorescent lamp glow?
1. As an arc current passes through the gas in the fluorescent tube, the electrons flowing from the electrode at the ends of the lamp collide with the mercury atoms that are in the gases of the lamp.
2. The impact of the electrons and the mercury atoms produces ultraviolet rays. These ultraviolet rays strike the phosphors on the glass wall of the lamp, causing them to fluoresce and produce visible light.
Fluorescent Ballast Basics
| 5
| 6Universal Lighting Technologies
Incandescent Lighting…. No Ballast
120 V
An incandescent lamp operates directly off the power line. Current flows through the filament,
and the filament glows, providing light. The filament also acts as a resistor to limit the current
passing through it.
Fluorescent Ballast Basics
| 6
| 7Universal Lighting Technologies
Which lamps need ballasts?
All arc discharge lamps such as fluorescent and high intensity discharge (HID) require ballasts for proper operation. Without a ballast, these lamps will not work.
Screw-in compact fluorescent lamps include an extremely small ballast built into the plastic base where the socket is located.
Circline Fluorescent
HIDCompact
FluorescentU-Bend
Fluorescent
Linear Fluorescent
Fluorescent Ballast Basics
| 7
| 8Universal Lighting Technologies
1. Supply power to preheat lamp filaments prior to starting (not required for instant start lamps)
2. Provide a high voltage to initiate an arc through the gas in the lamp
3. Control the lamp’s current to within its specifications to provide proper light output and rated life
BALLASTInput Voltage
1. Filament Heating
2. High Voltage Across the Lamp
3. Controls Current Going to the Lamp
The fluorescent lamps require a power device (ballast) that is connected to them to provide basic operating functions.
The Ballast’s Function
| 8
| 9Universal Lighting Technologies
Ballasts are an integral part of the lighting fixture. They are typically located within the fixture covered by a metal channel.
In down light fixtures for compact fluorescent lamps, the ballast is mounted on the outside of a junction box that is part of the lighting fixture.
Ballast Location
| 9
| 10Universal Lighting Technologies
Electromagnetic – The lowest efficiency
Electronic – The highest efficiency
There are primarily two categories of ballast constructions that define the technologies and materials used to manufacture the ballasts:
Fluorescent Ballast Types
| 10
| 11Universal Lighting Technologies
The first fluorescent lighting systems were developed with electromagnetic ballasts having two copper or aluminum wire coils assembled on steel laminations to create a transformer. The transformer was designed to provide the right voltage for starting and was usually connected with a capacitor to provide the proper lamp current.
Transformer with two coils assembled with laminations
Capacitor
Electromagnetic Ballasts
| 11
| 12Universal Lighting Technologies
Inefficient circuitry– Generates heat which wastes power– High operation costs compared to electronic ballasts– Operates lamps at power line frequency (60Hz)
Limited flexibility– Typically designed for one lamp or for two lamp operation – Common three or four lamp fixture requires two ballasts– Single product options, typically no alternatives depending upon application requirements
Lamps are connected in series, when one lamp fails, the other lamp extinguishes
Audible, sometimes annoying hum
Electromagnetic Technology
Due to their inefficient operation, magnetic ballasts for popular lamp applications have been outlawed by the Department of Energy, but there is still a large installed
base.
| 12
| 13Universal Lighting Technologies
The DC Voltage is then converted to a high frequency AC Voltage
The High frequency voltage is then increased to a higher voltage so that it can ignite the lamps while also being able to limit the lamp current
60 Hz Input
Alternating Current (AC) Voltage is converted to a Direct Current (DC) voltage, like a battery
High Frequency output > 20KHz
Electronic Ballasts operate the lamps at very high frequencies which improves lamp efficiencies and performance.
Components in an electronic ballast on a printed circuit board. (Components include transistors, diodes, capacitors, IC’s, resistors, etc.)
A block diagram is an easy way to explain how an electronic ballast operates
Electronic Ballasts
| 13
| 14Universal Lighting Technologies
– At low frequencies, fluorescent lamps actually re-ignite every half cycle of the input power’s sine wave, using additional energy.
– At high frequencies, the fluorescent lamp does not extinguish, saving energy by not having to re-ignite.
Actual Frequency Depicted is 1500 Hz
1/60 Second
Low Frequency and High Frequency Sine Waves
60Hz 200Hz 1KHz 5KHz 20KHz
Light output as frequency increases with constant lamp
power
Electronic ballasts are designed to take advantage of this by maintaining existing light levels and saving energy
The High Frequency Advantage
Fluorescent lamps increase in efficiency by more than 10% when operated at high frequency
| 14
| 15Universal Lighting Technologies
Efficient Operation
– Technology for lowest operating cost for fluorescent lighting
– High frequency lamp operation improves lamp efficiencies
Application Flexibility
– Products available for operating up to four lamps at once
– Most ballasts are designed for operating different lamp types and quantities
– Multiple product options to choose from depending upon application requirements
Quiet Operation
– The operating frequency of the lamps is higher than the human ear can hear.
Electronic Technology
| 15
| 16Universal Lighting Technologies
• Rapid Start – Magnetic & Electronic
• Instant Start– Magnetic & Electronic
• Programmed Start– Electronic Only
There are a number of different methods for starting fluorescent lamps.
T8 & T5 lamps may be started by more than one method. The following is a list of the starting methods and which ballast technologies employ these methods.
Instant Start and Programmed Start are the methods currently used for most lighting applications.
Starting Methods
| 17Universal Lighting Technologies
Rapid Start
Rapid Start ballasts provide filament voltage (heating) and lamp voltage simultaneously. When the lamp filaments reach a temperature that is sufficient for ignition with the lamp voltage applied, the lamps ignite.
–Glowing of the lamps is visible prior to ignition.–Depending upon the lamp voltage, this may not guarantee that the filament is sufficiently heated, resulting in poor lamp life. –Cathode voltage remains after the lamp has started consuming approximately 2 Watts per lamp.
It was believed that electronic rapid start ballasts would provide longer lamp life than instant start ballasts but this has been proven incorrect.
| 18Universal Lighting Technologies
Instant Start ballasts operate without heating the filaments. A high voltage is used to ignite the lamps. Instant start operation is more efficient since there is no additional power consumed for heating filaments.
–Single pin instant start (slimline) lamps must be instant started.
–Some Bi-pin lamps such as the F32T8 and F54T5HO can also be instant started.
Programmed Start is growing in popularity but Instant Start is still by far the largest segment.
Instant Start
| 19Universal Lighting Technologies
Programmed Start ballasts A.K.A Programmed Rapid Start
–Utilize electronic technology to provide optimal starting for lamps to achieve the longest lamp life possible.
–Tests have shown lamp life to be extended three times as long as traditional rapid start ballasts in applications where the lamps are frequently cycled on and off.
–Programmed Start ballasts can be used in place of rapid start ballasts since they usually wire the same way in the fixture, hence the addition of “Rapid” in the name.
Technology for long lamp life!
Programmed Start
| 20Universal Lighting Technologies
Step 1: Application of Filament Voltage (heating)– Lamp Voltage is kept very low to minimize glow current– Duration of Step 1 is approximately 800 milliseconds
• Assures that filament temperature is optimal for starting• Very low glow current during starting prevents damage to lamps
Step 2: Application of Starting Voltage to the Lamps– When the voltage is applied across the lamps, they quickly ignite since their filaments are already hot– Short transition prevents lamp damage by minimizing filament sputtering & end blackening
Step 3: Steady State Operation– Ballast regulates current through the lamp– Filament voltage is shut off or reduced to improve operating efficiency
How Programmed Start Circuits Work:
This technology incorporates a “programmed” starting sequence:
Programmed Start
| 20
| 21Universal Lighting Technologies
Which Electronic Ballast Starting is Best?
For the lamp types with a choice of starting methods: Identify the application and expected operating/switching cycle.
– Expected operating hours between starts.– Is the ballast connected to an occupancy sensor?
Use Programmed Start to maintain lamp life when: Ballasts are connected to occupancy sensors which will switch frequently. If the lighting is going to be switched on and off frequently.
– Typically less than three hours per start.
Use Instant start to maximize savings when: Ballasts are going to typically remain on for at least three hours between starts.
Best Starting Method
| 22Universal Lighting Technologies
Ballast Factor (BF) is also referred to as percent light output. It is a measurement of the ballast’s output and the light level it is driving or controlling the lamp at.
A ballast factor of 1.00 means that the lamp connected to the ballast will be operating at 100% of its rated lumens. Similarly, a ballast factor of .88 translates to 88% light output of the lamp.
The same lamp will provide different light levels when operated with different ballast factors.
BALLAST BALLAST
Low Ballast Factor Ballast High Ballast Factor Ballast
F32T8 Lamp F32T8 Lamp
Ballast Factor is a key component in determining the light output of a system
Ballast Factor
| 22
| 23Universal Lighting Technologies
Lamp F32T8
Rated Lamp Lumens 3000x Ballast Factor x 0.88x Number of Lamps x 3
System Lumens 7920
To calculate the lumens coming from a lamp/ballast system, the following equation is used:
The rated lamp lumens are found in lamp manufacturers catalogs The ballast factor is specified by the ballast manufacturer
System lumens for a 3-lamp F32T8 fixture with two magnetic ballasts:
Ballast Factor
| 23
| 24Universal Lighting Technologies
Per ANSI (American National Standards Institute) .925 is the minimum BF for a full light output magnetic ballast .85 is the minimum BF for a full light output electronic ballast
However, ballast factors can range from .60 to 1.20 Magnetic residential shoplite ballasts have had BFs as low as .60
– Hence the reason for poor light levels with these fixtures!
As Ballast Factor goes up . . . . . . the input power for the lighting system also goes up.
Ballast Factor
| 24
| 25Universal Lighting Technologies
0.88 - Standard Light Output T8– Common for new construction and retrofits– Used for frequently switched applications including occupancy sensors and daylight harvesting.– Good solution for education, commercial offices and retail.
0.78 - Low Power Instant Start T8– Used primarily for retrofit applications– Matches light levels of F40T12/ES (34W) systems– Applications include stairwells, hallways, bathrooms and other areas that are lit partially during the day.
1.18 - High Light Output T8– Used with New construction and retrofits– Ideal for de-lamp applications, high bay fixtures (including warehouses and manufacturing).– It is common for facilities to stock a single lamp and control light output for specific applications with
different BF ballasts.
As electronic ballast product lines continue to expand, their BF options continue to grow based on the different applications they are serving.
Electronic BF Options
| 25
| 26Universal Lighting Technologies
Ballast Type Magnetic Electronic Lamp F34T12 F32T8
Rated Lamp Lumens 2280 3000x Ballast Factor x 0.90 x 0.78x Number of Lamps x 4 x 4
System Lumens 8208 9630
A Ballast Factor of .78 with an F32T8 provides more lumens than the F34T12 lamp with a magnetic ballast (.90 BF)
If more light output is needed, a higher ballast factor ballast can be installed but it will use more energy.
The example below compares the lumens before and after a lighting retrofit.
Retrofit Example
© 2013 Universal Lighting Technologies | 26
| 27Universal Lighting Technologies
Ballast input circuit draws current from the power line and internally regulates the DC voltage within the ballast. As a result of the regulated DC voltage, the output to the lamps remains constant.
Ballasts operate from 108 to 305 Volts, 50 or 60 Hertz.– 120 (-10%) to 277 (+10%)– Installer Friendly, two wires, no special taps
Electronic ballast technology has lead to the development of ballasts that can be connected to different input voltages. This simplifies inventory carrying requirements and prevents wiring a ballast to the wrong input voltage.
How it works:
Universal Input Voltage
Universal input voltage is now common and available for a wide variety of lamp applications.
© 2013 Universal Lighting Technologies | 27
| 28Universal Lighting Technologies
Series:All Magnetic & Some Electronic
Parallel:Available only with electronic
Some ballasts operate the lamps in series, some in parallel:
When one lamp fails, the other lamps extinguish.
When one lamp fails, the other lamps remain “on.”
Lamp Configuration: Series VS. Parallel
© 2013 Universal Lighting Technologies | 28
| 29Universal Lighting Technologies
Ballasts are selected based upon the application– Identify voltage (Typically 120 or 277 volts)– Identify lamp type– Identify the quantity of lamps the ballast operates
Refer to Navigator Catalog, Ballast selector Guide or online BallastSpecs, and using the application information from above, identify the appropriate ballast
Refer to cross references available on www.unvlt.com
Selecting a Replacement Ballast
© 2013 Universal Lighting Technologies | 29
| 30Universal Lighting Technologies
THANK YOU
For Additional Information, please visit our website www.unvlt.com or use your QR Reader for Smart Phone instant access.
| 30
Website: www.unvlt.comNashville Customer Service: (800) 862-8666
Universal Technical Engineering Services: 1-800-BALLAST (1-800-225-5278)